Plan Review Notes For Permit 08040824
Permit Number 08040824
Review Stop G
Sequence Number 4
Notes
Date Text
2008-08-27 16:39:52 
  
  
 PASSED/PROVISO
  
 MANUF. SPEC. SHEETS FOR THE WATER HEATER AND THE PIZZA
 OVEN NOT SUBMITTED. SUBMIT AT TIME OF GAS PERMIT
 APPLICATION.
  
 GAS PIPING NOT CORRECT. 2-1/2" REQUIRED TO ITEM 17.--
 1-1/4" REQUIRED TO SHUT OFF VALVE FOR WATER HEATER--
 2" REQUIRED TO ITEM 13,--1-1/2" REQUIRED TO ITEM
 10.--1-1/4" MINIMUM REQUIRED THRU ITEM 9 INCLUDING
 SHUT OFF VALVE.--1-14" REQUIRED FOR SUPPLY AND SHUT
 OFF VALVE FOR ITEM 10.--1" REQUIRED FOR SUPPLY AND
 SHUT OFF VALVE FOR ITEM 13.--1" REQUIRED FOR SUPPLY
 AND SHUT OFF VALVE FOR ITEM 15.--1-14" REQUIRED FOR
 SUPPLY AND SHUT OFF VALVE FOR ITEM 17. ---A
 REVISION IS REQUIRED FOR SHT P-2 GAS RISER DIAGRAM
 REFLECTING THESE AS SOON AS POSSIBLE.
  
  
  
  
  
 .