Plan Review Notes
Plan Review Notes For Permit 08040824
Permit Number 08040824
Review Stop E
Sequence Number 4
Notes
Date Text
2008-09-02 10:36:41 
  
  
  
  
 ** DENIED 4TH REVIEW **
  
  
 **** PLEASE SEE COMMENTS BELOW WHICH ARE THE SAME AS
 PREVIOUS REVIEWS.
  
  
 1) NOTE: PLANS STILL DO NOT STATE ANY MAXIMUM OVER RIDE
 TIMES OR MAXIMUM OCCUPANCY SENSOR TIMES. THE NEW *KP*
 KEY PAD AS NOTED ON SHEET E-4 AND ON SYMBOL LEGEND DOES
 NOT CONTAIN ANY TIMES. THE OCCUPANCY SENSORS AS NOTED
 ON SYMBOL LEGEND DOES NOT CONTAIN ANY TIMES.
 PLEASE STATE THE REQUIRED *MAXIMUM* OVER RIDE TIMES PER
 THE SAME SECTIONS.
 PLEASE SEE 13-415.1.ABC.1.1,.1.2, .1.3.
 (( IF TIMED OVER RIDE, MUST BE A MAXIMUM OF FOUR HOURS
 OR LESS) (IF AN OCCUPANCY SENSOR IS USED FOR OVER RIDE,
 TIME IS A MAXIMUM OF 30MINUTES OR LESS)
  
 2) NOTE: PLEASE SEE 13-415.2.ABC.1.1, .1.2, 13-415.2.B,
 13-415.2, 13-415.2, 13-415.2.ABC.1, 13-415.2.C ETC. THE
 ENTIRE SECTION OF 13-415.2 APPLIES.
 PLEASE KNOW ON PREVIOUS CORRESPONDENCE THE LIGHTING
 PERFORMANCE CALCULATIONS GOING TO BE PLACED ON PLANS
 HOWEVER SHEETS E-1-E-6 AND ELP-1 DO NOT CONTAIN ANY
 LIGHTING CALCULATIONS TO REVIEW AND COMPARE TO THE
 LIGHTING AS SHOWN ON PLANS.
 PLEASE BE SURE TO SEE THE TRACK LIGHTING SECTIONS OF
 THE CODE.
 PLEASE SEE SPACE BY SPACE METHOD FOR DINING ALLOWANCES,
 OTHER SPACES, DECORATIVE ETC.
 CALLED AND SPOKE TO ELECTRICAL ENGINEER AND MECHANICAL
 ENGINEER. CALCULATIONS ARE REQUIRED TO MEET
 PRESCRIPTIVE REQUIREMENTS.
 BASED ON THE PLANS SUBMITTED THE LIGHTING AS SHOWN DOES
 NOT PROVIDE THE MINIMUM INFORMATION WHICH IS REQUIRED.
 PLEASE BE SURE TO SEE 13-415.2.ABC.1.1, AND .1.2 AS
 NOTED ABOVE FOR TRACK LIGHTING AND THE VA RATINGS FOR
 FIXTURES AND VA RATINGS FOR TRACK TO BE USED.
 *** PLEASE KEEP IN MIND LINE VOLTAGE TRACK VA WATTAGE
 IS BASED ON VA PER FIXTURE TIMES THE NUMBER OF FIXTURES
 ON PLANS OR 30VA PER FOOT OF TRACK,,,,,, (WHICH EVER IS
 GREATER).
 *** PLEASE SEE LOW VOLTAGE TRACK VA IS BASED ON THE
 REMOTE TYPE TRANSFORMER RATING.
 ** PLEASE BE SURE TO COMPLETE THE FIXTURE SCHEDULE WITH
 THE TRACK LIGHTING AS NOTED ON SYMBOL LEGEND.
  
 3) NOTE: PLEASE KNOW AS REQUIRED BY FLORIDA STATUTES
 553.80(2)(B) A FEE IS NOW ASSESSED BASED ON REPEAT
 COMMENTS FOR CODE COMPLIANCE. THIS IS A *STATUTORY*
 REQUIRED FEE AND IS NOT A LOCAL ENFORCEMENT RULING. THE
 FEE AMOUNT IS BASED ON 4X THE PLAN REVIEW PORTION OF
 THE BASE PERMIT FEE. IN THIS CASE THE BASE PERMIT FEE
 IS $7,300.00. THE PLAN REVIEW PORTION OF THIS FEE IS 30
 PERCENT WHICH IS $2,190.00. THAT IS THE FEE TIMES FOUR.
 THIS COMES TO $9,300.00 WHICH IS REQUIRED TO BE PAID.
 ONCE AGAIN THIS IS A *STATE* REQUIRED FEE AND IS NOT A
 LOCAL REQUIREMENT. THE SECTION OF THE FLORIDA STATUTES
 IS ATTACHED TO THE PLAN REVIEW NOTES.
 ** ONE SET OF ELECTRICAL PLANS ARE RETAINED ONCE AGAIN
 FOR FILE.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  