| Date |
Text |
| 2008-08-12 16:53:58 | |
| | ** DENIED PLANS. ** |
| | |
| | |
| | 1) NOTE: NEW *KP* KEY PAD AS NOTED FOR |
| | 13-415.1.ABC.1.1, .1.2. PLEASE STATE THE REQUIRED |
| | *MAXIMUM* OVER RIDE TIMES PER THE SAME SECTIONS. |
| | (( IF TIMED OVER RIDE, MUST BE A MAXIMUM OF FOUR HOURS) |
| | (IF AN OCCUPANCY SENSOR IS USED FOR OVER RIDE, TIME IS |
| | A MAXIMUM OF 30MINUTES) |
| | |
| | 2) NOTE: PLEASE SEE 13-415.2.ABC.2.1, .1.2, 13-415.2.B, |
| | 13-415.2, 13-415.2, 13-415.2.ABC.1. PLEASE SEE SECTIONS |
| | AS NOTED MAY NOT USE THE EXCEPTION IN THE CODE FOR THIS |
| | OCCUPANCY. PLEASE SEE SPACE BY SPACE METHOD FOR DINING |
| | ALLOWANCES, OTHER SPACES, DECORATIVE ETC. |
| | CALLED AND SPOKE TO ELECTRICAL ENGINEER AND MECHANICAL |
| | ENGINEER. THEY WILL BE REFIGURING CALCULATIONS TO MEET |
| | PRESCRIPTIVE REQUIREMENTS. |
| | BASED ON THE CALCULATIONS SUBMITTED THE DESIGN WATTAGE |
| | EXCEEDS THE ALLOWANCES BASED ON THIS OCCUPANCY. |
| | PLEASE BE SURE TO SEE 13-415.2.ABC.1.1, AND .1.2 AS |
| | NOTED ABOVE FOR TRACK LIGHTING AND THE VA RATINGS FOR |
| | FIXTURES AND VA RATINGS FOR TRACK TO BE USED. |
| | *** PLEASE KEEP IN MIND LINE VOLTAGE TRACK VA WATTAGE |
| | IS BASED ON VA PER FIXTURE TIMES THE NUMBER OF FIXTURES |
| | ON PLANS OR 30VA PER FOOT OF TRACK,,,,,, (WHICH EVER IS |
| | GREATER). |
| | *** PLEASE SEE LOW VOLTAGE TRACK VA IS BASED ON THE |
| | REMOTE TYPE TRANSFORMER RATING. |
| | ** PLEASE BE SURE TO COMPLETE THE FIXTURE SCHEDULE WITH |
| | THE TRACK LIGHTING AS NOTED ON SYMBOL LEGEND. |
| | |
| | ENGINEER WILL SEND PDF TO MAKE SURE CALCULATIONS ARE |
| | SET UP FOR SPACE BY SPACE AREAS. THE E-MAILING OF THE |
| | PDF WILL NOT CONSTITUTE AS A TECHNICAL REVIEW OF CODE |
| | LIGHTING CALCULATIONS FOR THE ENERGY CODE. THIS WILL BE |
| | TO HELP WITH A SET UP OF PERFORMANCE CALCULATIONS. |
| | |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |