Plan Review Notes
Plan Review Notes For Permit 08040824
Permit Number 08040824
Review Stop E
Sequence Number 3
Notes
Date Text
2008-08-12 16:53:58 
 ** DENIED PLANS. **
  
  
 1) NOTE: NEW *KP* KEY PAD AS NOTED FOR
 13-415.1.ABC.1.1, .1.2. PLEASE STATE THE REQUIRED
 *MAXIMUM* OVER RIDE TIMES PER THE SAME SECTIONS.
 (( IF TIMED OVER RIDE, MUST BE A MAXIMUM OF FOUR HOURS)
 (IF AN OCCUPANCY SENSOR IS USED FOR OVER RIDE, TIME IS
 A MAXIMUM OF 30MINUTES)
  
 2) NOTE: PLEASE SEE 13-415.2.ABC.2.1, .1.2, 13-415.2.B,
 13-415.2, 13-415.2, 13-415.2.ABC.1. PLEASE SEE SECTIONS
 AS NOTED MAY NOT USE THE EXCEPTION IN THE CODE FOR THIS
 OCCUPANCY. PLEASE SEE SPACE BY SPACE METHOD FOR DINING
 ALLOWANCES, OTHER SPACES, DECORATIVE ETC.
 CALLED AND SPOKE TO ELECTRICAL ENGINEER AND MECHANICAL
 ENGINEER. THEY WILL BE REFIGURING CALCULATIONS TO MEET
 PRESCRIPTIVE REQUIREMENTS.
 BASED ON THE CALCULATIONS SUBMITTED THE DESIGN WATTAGE
 EXCEEDS THE ALLOWANCES BASED ON THIS OCCUPANCY.
 PLEASE BE SURE TO SEE 13-415.2.ABC.1.1, AND .1.2 AS
 NOTED ABOVE FOR TRACK LIGHTING AND THE VA RATINGS FOR
 FIXTURES AND VA RATINGS FOR TRACK TO BE USED.
 *** PLEASE KEEP IN MIND LINE VOLTAGE TRACK VA WATTAGE
 IS BASED ON VA PER FIXTURE TIMES THE NUMBER OF FIXTURES
 ON PLANS OR 30VA PER FOOT OF TRACK,,,,,, (WHICH EVER IS
 GREATER).
 *** PLEASE SEE LOW VOLTAGE TRACK VA IS BASED ON THE
 REMOTE TYPE TRANSFORMER RATING.
 ** PLEASE BE SURE TO COMPLETE THE FIXTURE SCHEDULE WITH
 THE TRACK LIGHTING AS NOTED ON SYMBOL LEGEND.
  
 ENGINEER WILL SEND PDF TO MAKE SURE CALCULATIONS ARE
 SET UP FOR SPACE BY SPACE AREAS. THE E-MAILING OF THE
 PDF WILL NOT CONSTITUTE AS A TECHNICAL REVIEW OF CODE
 LIGHTING CALCULATIONS FOR THE ENERGY CODE. THIS WILL BE
 TO HELP WITH A SET UP OF PERFORMANCE CALCULATIONS.
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved