Plan Review Notes
Plan Review Notes For Permit 08040824
Permit Number 08040824
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2008-07-23 10:34:21***DENIED***
  
 SOME OF THE PREVIOUS COMMENTS HAVE BEEN ADDRESSED.
 PLEASE SEE THE FOLLOWING FOR CORRECTION:
  
 01. IN ADDITION TO DEMOLITION, THIS REQUIREMENT APPLIES
 TO CONSTRUCTION AND ALTERATION. (NFPA 241)
  
 02. OK
  
 03. OK
  
 04. PLANS STILL DO NOT CLEARLY ILLUSTRATE COMPLIANCE
 WITH REQUIREMENT REGARDING PANIC AND FIRE EXIT
 HARDWARE. SEE THE DOOR SCHEDULE UNDER PANIC COLUMN.
 PLEASE ADD SPECIFIC INFORMATION TO DOOR SHEDULE.
  
 05. OK
  
 06. OK
  
 07. OK
  
 08. OK
  
 09. OK
  
 10. OK
  
 11. THE FIRE ALARM SCOPE STILL REFERENCES THE 1999
 EDITION. FIRE ALARM SHALL COMPLY WITH NFPA 72, 2002
 EDITION. PLEASE REMOVE EARLIER CODE CYCLE REFERENCE.
  
 12. OK
  
 13. NOT ADDRESSED. PLEASE ADD NOTE NFPA 13, 2002
 EDITION TO GOVERNING CODE OR FIRE SPRINKLER SHEET
 FS-1.
  
 14. NOT ADDRESSED. THE SUBMITTED PLAN SHEETS DO NOT
 ACTUALLY CORRELATE WITH THE LIST OF DRAWINGS AS SHOWN
 ON SHEET A1.0.
  
  
 NEW COMMENTS:
  
 01. OCCUPANT LOAD SIGN WILL BE REQUIRED AT TIME OF FIRE
 FINAL INSPECTION. CONTACT WPB BUREAU OF FIRE PREVENTION
 AT (561) 804-4724 FOR ASSISTANCE.
  
 02. PLEASE PROVIDE LIFE SAFETY SHEET ILLUSTRATING MAX.
 TRAVEL DISTANCE COMPLIANCE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756