Date Text
2008-07-25 16:42:30 
 ** DENIED2ND REVIEW **
  
 *** PLEASE KNOW IT IS IMPORTANT TO KNOW THERE ARE
 SEVERAL ITEMS WHICH ARE FROM PREVIOUS REVIEW WHICH ARE
 STILL IN NEED OF ADDRESSING.
 PLEASE ALSO SEE NOTES BELOW AS THERE ARE ALSO NEW
 COMMENTS AS THERE HAVE BEEN REVISIONS MADE TO PLANS
 WHICH WERE NOT PART OF THE PREVIOUS REVIEWED PLANS.
  
 ** THERE IS INFORMATION STILL NOT YET SUBMITTED
 THEREFORE A COMPLETE REVIEW FOR CODE COMPLIANCE CAN NOT
 POSSIBLY BE DONE.
  
  
 1) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #3. THE ADA
 LEVELS FOR STROBES WERE SHOWN HOWEVER WHERE IS THE
 AUDIBLE LEVELS?
 FBC 11-4.28.1, .2 AN D.3(4).
  
 2) NOTE: PLEASE SEEPREVIOUS REVIEW NOTE #4. NOW A
 SUBMITTED FLA COM METHOD *B* IS BEING SUBMITTED. THE
 SECTIONS OF THE CODE WERE GIVEN ON PREVIOUS REVIEW FOR
 DEFINITIONS OF THE SCOPE OF WORK. THIS TENANT
 RENOVATION DOES NOT APPEAR TO QUALIFY AS A RENOVATION
 TO THE BUILDING. THE LIGHTING PERFORMANCE PARTOF
 TABLE *B* AND SECTIONS 13-415.2.ABC.1.1,.1.2 AND .1.3
 NEED TO BE MET. THIS IS NOT YET DONE.
 PLEASE ALSO SEE THE METHOD OF CONTROLS IS STILL SHOWN
 AS MANUAL ON OFF AND CONTINUOUS DIMMING. THIS IS NOT
 POSSIBLE.
 .
 PLEASE SEE 13-101.1.1, 13-101.1.2,13-101.3,
 13-400.0.A,13-400.0.B, 13-400.0.C,ETC.
 PLEASE SEE MECHANICAL REVIEW COMMENTS WITH RESPECT TO
 MINIMUM REQUIREMENTS REQUIRED.
 THIS COMMENT IS GIVEN FOR INFORMATION FOR ALL OTHER
 TRADES HOWEVER ELECTRICAL COMPLIANCE WITH SECTIONS
 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3 NEED TO BE
 MET.
 THE INPUT DATA REPORT IS REQUIRED TO COORDINATE WITH
 PLANS. HOW IS THIS POSSIBLE WHEN THERE ARE SEVERAL
 ITEMS IN THE IDR WHICH ARE BLANK OR SHOWING OTHER
 INFORMATION THAN WHAT IS ON PLANS. IDR SHOWS ONLY ONE
 WALL, HOW IS THIS POSSIBLE? IDR SHOWS NO DOORS FROM
 CONDITIONED TO UNCONDITIONED SPACE, HOW IS THIS
 POSSIBLE. THE IDR SHOWS NO FLOORS, HOW IS THIS
 POSSIBLE?THERE IS HOT WATER SYSTEMS YET THE PIPING
 INSULATION IS BLANK, HOW IS THIS POSSIBLE. THESE ARE A
 FEW EXAMPLES.
 PLEASE SEE THE INFORMATION ON THE INPUT DATA REPORTS IS
 REQUIRED TO COORDINATE WITH PLANS COMPLETELY.
  
 3) NOTE: PLEASE SEEPREVIOUS NOTES AND
 SECTIONS13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4.
 PLANS DO NOT SHOW ENOUGH INFORMATION FOR ANY TIMED
 SCHEDULING SYSTEM. PLANS STILL SHOW NUMEROUS LOCATIONS
 WHERE STANDARD SINGLE POLE SWITCHES ARE STILL BEING
 SHOWN. HOW DO THESE STANDARD DINGLE POLE DEVICES MEET
 THE *MINIMUM* REQUIRED BY CODE WHEN THEY DO NOT MEET
 THE SECTIONS NOTED?
 SOME EXAMPLES BELOW ARE TAKEN DIRECTLY FROM PREVIOUS
 REVIEW NOTES.
  
 A) PLEASE VERIFY ALL OVER RIDE LOCATIONS REQUIRED.
 PLEASE SEE THAT AN OCCUPANT MUST BE ABLE TO OVER RIDE
 ANY TIME OF DAY SCHEDULING AT THE POINT OF ENTRANCE
 INTO ANY ONE SPACE. THE OCCUPANT MUST BE ABLE TO SEE
 ALL LIGHTING WHICH IS BEING CONTROLLED OR NEEDS TO MEET
 EXCEPTIONS.
  
 B) PLEASE SEE SOME LIGHTING CONTROLS SHOWN ON PLANS ARE
 STANDARD SWITCHES. HOW IS THIS POSSIBLE WHEN AUTOMATED
 CONTROLS ARE REQUIRED?
 SOME LOCATION EXAMPLES ARE HALL, ACCENT LIGHTS, LIQUOR
 STORAGE, CLOSET ETC
 ** THIS IS NOT ALL LOCATIONS AS THERE ARE OTHERS. ONLY
 SOME ARE GIVEN AS EXAMPLES.
  
 C) PLEASE SEE PLANS ARE MISSING REQUIRED SEPARATE SPACE
 CONTROLS. THESE ARE REQUIRED TO BE AUTOMATED OR PART OF
 A SYSTEM WITH OVER RIDES.
  
 D) PLEASE PROVIDE A COMPLETE SYSTEM/ETC FOR MINIMUM
 LIGHTING CONTROLS AS REQUIRED PER SECTIONS ABOVE.
 PLEASE PROVIDE COMPLETE SCHEDULE OF SYSTEM, SCHEDULE
 FOR ALL ITEMS ON THE DIMMING PANEL.
 AS NO SCHEDULE WAS SUBMITTED THERE ARE SEVERAL ITEMS
 WHICH CAN NOT BE DETERMINED FOR CODE COMPLIANCE WITH
 REQUIRED LIGHTING CONTROLS AS WELL AS OTHER COMMENTS.
 PLEASE SEE THE FOLLOWING COMMENT.
 PLEASE KNOW COMPLETE COMPLIANCE FOR AUTOMATED LIGHTING
 CONTROLS IS REQUIRED.THIS IS A BUILDING OVER 5000 SQ
 FT.
  
  
 4) NOTE: PLEASE KNOW AS PLANS CLEARLY INDICATE NORMAL
 LIGHTING BEING CONTROLLED THROUGH A DIMMING PANEL OF
 SOME KIND PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR
 EGRESS PATHS FOR MINIMUM LIGHTING LEVELS.
 PLEASE KNOW THE MINIMUM LEVELS FOR LIGHTING SHALL NOT
 BE PERMITTED TO DIM BELOW THE 1FT CANDLE REQUIRED BY
 THE LIFE SAFETY CODE, NFPA-101 7.8, 7.9. 7.8.1.3
 PLEASE PROVIDE MORE INFORMATION. THIS WAS NOT
 SUBMITTED. THE PLANS NOW INDICATE A NOTE WHICH STATES
 LIGHTING LEVELS MUST MEET CODE HOWEVER IF THE DIMMING
 SYSTEM IS NOT DESIGNED TO BE SPECIFIC THE LIGHTING
 LEVELS MAY VERY WELL BE DIMMED TO A LIGHTING LEVEL OF
 *0* WHEN OCCUPIED UNDER NORMAL CONDITIONS. PLEASE
 DESIGN/SPECIFY THE DEVICE SET LEVELS ETC
 FBC 106.1.2.
 FAC 61G15-33.004
  
 5) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS ON
 THE EXISTING 1000AMP MAIN IN WHICH THE PROPOSED
 SERVICE. PLEASE SEE THE NEXT FEW NOTES AS THE RISER HAS
 BEEN COMPLETELY REVISED AND THERE WILL BE COMMENTS
 BELOW WHICH WILL AFFECT SERVICE LOADS CALCULATIONS..
 PLEASE OBTAIN ALL RECENT LOADS WHICH HAVE BEEN ADDED TO
 BUILDING AND POSSIBLY THIS SERVICE.
 PLEASE SEE 220.87. A LOAD STUDY MAY NOT BE ACCURATE AS
 NEW LOADS HAVE CONTINUALLY BEEN ADDED AND SOME LOADS
 HAVE NOT BEEN COMPLETED ON SERVICE.
 PLEASE SEE CODES REFLECTED ON THE CALCULATIONS NEED TO
 COORDINATE WITH CODE. PLEASE VERIFY 220.44 AS NOTED FOR
 ALL OTHER LOADS. HOW ARE LIGHTING LOADS UNDER THIS SAME
 CODE SECTION?
 PLEASE SEE 220.42 AND 220.43.
  
 6) NOTE:PLEASE SEE PREVIOUS REVIEW NOTE #9. TRACK
 LIGHTING LOADS ARE STILL NOT SHOWN.
 PLEASE SEE NOTE #5 ABOVE IN WHICH SECTION 220.43 WAS
 BRIEFLY SATED FOR LOAD CALCULATIONS. PLEASE SHOW ALL
 TRACK LIGHTING LOADS AND HOW THEY ARE DERIVED. AS THESE
 ARE SPECIFIED AT THIS TIME COMPLIANCE CAN NOT BE
 VERIFIED. THIS WILL AFFECT THE DIMMER PANELS.
  
 7) NOTE: PLEASE SEE PREVIOUS NOTE #10. PLEASE SEE THESE
 WERE NOT REVISED. TO MEET THE EXCEPTION IN THE CODE
 ONLY A SPECIFIC BREAKER MAY BE USED. A SNAP ON TYPE
 DEVICE IS NOT LISTED FOR PERMANENT INSTALLATION. PLEASE
 SEE 700.12F FOR CIRCUITING OF EMERGENCY LIGHTS. THESE
 SHALL BE CIRCUITED TO THE LOCAL BRANCH CIRCUIT IN ANY
 ONE AREA.
  
 8) NOTE: PLEASE SEE NEW RISER AS TENANT IS NOW SHOWN
 BEING FED FROM TWO COMPLETELY SEPARATE SERVICES WHICH
 IS NOT PERMITTED.
 THERE ARE NO SEPARATE VOLTAGES ETC WHICH WOULD REQUIRE
 THE ELECTRICAL TO BE FED FROM SEPARATE SERVICES. THERE
 ARE NO OTHER EXCEPTIONS SHOWN TO JUSTIFY.
 PLEASE KNOW THE FIRE MARSHAL ALSO HAS CONCERN OVER
 MULTIPLE MAIN DISCONNECTS FOR ONE TENANT. NO SIGNAGE,
 NO NOTES, NO INFORMATION OF LABELING ETC IS SHOWN. AS
 NOTED ABOVE NO LOAD CALCULATIONS ETC WERE SUBMITTED. AS
 THIS IS NO COMPLETE AT THIS TIME THERE ARE MANY
 UNANSWERED QUESTIONS.
 230, 240, 220 ET
  
 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. PLEASE KNOW ONE
 SET OF ELECTRICAL PLANS HAVE BEEN RETAINED BY THIS
 OFFICE/REVIEWER.
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]