| 2008-07-25 16:42:30 | |
| | ** DENIED2ND REVIEW ** |
| | |
| | *** PLEASE KNOW IT IS IMPORTANT TO KNOW THERE ARE |
| | SEVERAL ITEMS WHICH ARE FROM PREVIOUS REVIEW WHICH ARE |
| | STILL IN NEED OF ADDRESSING. |
| | PLEASE ALSO SEE NOTES BELOW AS THERE ARE ALSO NEW |
| | COMMENTS AS THERE HAVE BEEN REVISIONS MADE TO PLANS |
| | WHICH WERE NOT PART OF THE PREVIOUS REVIEWED PLANS. |
| | |
| | ** THERE IS INFORMATION STILL NOT YET SUBMITTED |
| | THEREFORE A COMPLETE REVIEW FOR CODE COMPLIANCE CAN NOT |
| | POSSIBLY BE DONE. |
| | |
| | |
| | 1) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #3. THE ADA |
| | LEVELS FOR STROBES WERE SHOWN HOWEVER WHERE IS THE |
| | AUDIBLE LEVELS? |
| | FBC 11-4.28.1, .2 AN D.3(4). |
| | |
| | 2) NOTE: PLEASE SEEPREVIOUS REVIEW NOTE #4. NOW A |
| | SUBMITTED FLA COM METHOD *B* IS BEING SUBMITTED. THE |
| | SECTIONS OF THE CODE WERE GIVEN ON PREVIOUS REVIEW FOR |
| | DEFINITIONS OF THE SCOPE OF WORK. THIS TENANT |
| | RENOVATION DOES NOT APPEAR TO QUALIFY AS A RENOVATION |
| | TO THE BUILDING. THE LIGHTING PERFORMANCE PARTOF |
| | TABLE *B* AND SECTIONS 13-415.2.ABC.1.1,.1.2 AND .1.3 |
| | NEED TO BE MET. THIS IS NOT YET DONE. |
| | PLEASE ALSO SEE THE METHOD OF CONTROLS IS STILL SHOWN |
| | AS MANUAL ON OFF AND CONTINUOUS DIMMING. THIS IS NOT |
| | POSSIBLE. |
| | . |
| | PLEASE SEE 13-101.1.1, 13-101.1.2,13-101.3, |
| | 13-400.0.A,13-400.0.B, 13-400.0.C,ETC. |
| | PLEASE SEE MECHANICAL REVIEW COMMENTS WITH RESPECT TO |
| | MINIMUM REQUIREMENTS REQUIRED. |
| | THIS COMMENT IS GIVEN FOR INFORMATION FOR ALL OTHER |
| | TRADES HOWEVER ELECTRICAL COMPLIANCE WITH SECTIONS |
| | 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3 NEED TO BE |
| | MET. |
| | THE INPUT DATA REPORT IS REQUIRED TO COORDINATE WITH |
| | PLANS. HOW IS THIS POSSIBLE WHEN THERE ARE SEVERAL |
| | ITEMS IN THE IDR WHICH ARE BLANK OR SHOWING OTHER |
| | INFORMATION THAN WHAT IS ON PLANS. IDR SHOWS ONLY ONE |
| | WALL, HOW IS THIS POSSIBLE? IDR SHOWS NO DOORS FROM |
| | CONDITIONED TO UNCONDITIONED SPACE, HOW IS THIS |
| | POSSIBLE. THE IDR SHOWS NO FLOORS, HOW IS THIS |
| | POSSIBLE?THERE IS HOT WATER SYSTEMS YET THE PIPING |
| | INSULATION IS BLANK, HOW IS THIS POSSIBLE. THESE ARE A |
| | FEW EXAMPLES. |
| | PLEASE SEE THE INFORMATION ON THE INPUT DATA REPORTS IS |
| | REQUIRED TO COORDINATE WITH PLANS COMPLETELY. |
| | |
| | 3) NOTE: PLEASE SEEPREVIOUS NOTES AND |
| | SECTIONS13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4. |
| | PLANS DO NOT SHOW ENOUGH INFORMATION FOR ANY TIMED |
| | SCHEDULING SYSTEM. PLANS STILL SHOW NUMEROUS LOCATIONS |
| | WHERE STANDARD SINGLE POLE SWITCHES ARE STILL BEING |
| | SHOWN. HOW DO THESE STANDARD DINGLE POLE DEVICES MEET |
| | THE *MINIMUM* REQUIRED BY CODE WHEN THEY DO NOT MEET |
| | THE SECTIONS NOTED? |
| | SOME EXAMPLES BELOW ARE TAKEN DIRECTLY FROM PREVIOUS |
| | REVIEW NOTES. |
| | |
| | A) PLEASE VERIFY ALL OVER RIDE LOCATIONS REQUIRED. |
| | PLEASE SEE THAT AN OCCUPANT MUST BE ABLE TO OVER RIDE |
| | ANY TIME OF DAY SCHEDULING AT THE POINT OF ENTRANCE |
| | INTO ANY ONE SPACE. THE OCCUPANT MUST BE ABLE TO SEE |
| | ALL LIGHTING WHICH IS BEING CONTROLLED OR NEEDS TO MEET |
| | EXCEPTIONS. |
| | |
| | B) PLEASE SEE SOME LIGHTING CONTROLS SHOWN ON PLANS ARE |
| | STANDARD SWITCHES. HOW IS THIS POSSIBLE WHEN AUTOMATED |
| | CONTROLS ARE REQUIRED? |
| | SOME LOCATION EXAMPLES ARE HALL, ACCENT LIGHTS, LIQUOR |
| | STORAGE, CLOSET ETC |
| | ** THIS IS NOT ALL LOCATIONS AS THERE ARE OTHERS. ONLY |
| | SOME ARE GIVEN AS EXAMPLES. |
| | |
| | C) PLEASE SEE PLANS ARE MISSING REQUIRED SEPARATE SPACE |
| | CONTROLS. THESE ARE REQUIRED TO BE AUTOMATED OR PART OF |
| | A SYSTEM WITH OVER RIDES. |
| | |
| | D) PLEASE PROVIDE A COMPLETE SYSTEM/ETC FOR MINIMUM |
| | LIGHTING CONTROLS AS REQUIRED PER SECTIONS ABOVE. |
| | PLEASE PROVIDE COMPLETE SCHEDULE OF SYSTEM, SCHEDULE |
| | FOR ALL ITEMS ON THE DIMMING PANEL. |
| | AS NO SCHEDULE WAS SUBMITTED THERE ARE SEVERAL ITEMS |
| | WHICH CAN NOT BE DETERMINED FOR CODE COMPLIANCE WITH |
| | REQUIRED LIGHTING CONTROLS AS WELL AS OTHER COMMENTS. |
| | PLEASE SEE THE FOLLOWING COMMENT. |
| | PLEASE KNOW COMPLETE COMPLIANCE FOR AUTOMATED LIGHTING |
| | CONTROLS IS REQUIRED.THIS IS A BUILDING OVER 5000 SQ |
| | FT. |
| | |
| | |
| | 4) NOTE: PLEASE KNOW AS PLANS CLEARLY INDICATE NORMAL |
| | LIGHTING BEING CONTROLLED THROUGH A DIMMING PANEL OF |
| | SOME KIND PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR |
| | EGRESS PATHS FOR MINIMUM LIGHTING LEVELS. |
| | PLEASE KNOW THE MINIMUM LEVELS FOR LIGHTING SHALL NOT |
| | BE PERMITTED TO DIM BELOW THE 1FT CANDLE REQUIRED BY |
| | THE LIFE SAFETY CODE, NFPA-101 7.8, 7.9. 7.8.1.3 |
| | PLEASE PROVIDE MORE INFORMATION. THIS WAS NOT |
| | SUBMITTED. THE PLANS NOW INDICATE A NOTE WHICH STATES |
| | LIGHTING LEVELS MUST MEET CODE HOWEVER IF THE DIMMING |
| | SYSTEM IS NOT DESIGNED TO BE SPECIFIC THE LIGHTING |
| | LEVELS MAY VERY WELL BE DIMMED TO A LIGHTING LEVEL OF |
| | *0* WHEN OCCUPIED UNDER NORMAL CONDITIONS. PLEASE |
| | DESIGN/SPECIFY THE DEVICE SET LEVELS ETC |
| | FBC 106.1.2. |
| | FAC 61G15-33.004 |
| | |
| | 5) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS ON |
| | THE EXISTING 1000AMP MAIN IN WHICH THE PROPOSED |
| | SERVICE. PLEASE SEE THE NEXT FEW NOTES AS THE RISER HAS |
| | BEEN COMPLETELY REVISED AND THERE WILL BE COMMENTS |
| | BELOW WHICH WILL AFFECT SERVICE LOADS CALCULATIONS.. |
| | PLEASE OBTAIN ALL RECENT LOADS WHICH HAVE BEEN ADDED TO |
| | BUILDING AND POSSIBLY THIS SERVICE. |
| | PLEASE SEE 220.87. A LOAD STUDY MAY NOT BE ACCURATE AS |
| | NEW LOADS HAVE CONTINUALLY BEEN ADDED AND SOME LOADS |
| | HAVE NOT BEEN COMPLETED ON SERVICE. |
| | PLEASE SEE CODES REFLECTED ON THE CALCULATIONS NEED TO |
| | COORDINATE WITH CODE. PLEASE VERIFY 220.44 AS NOTED FOR |
| | ALL OTHER LOADS. HOW ARE LIGHTING LOADS UNDER THIS SAME |
| | CODE SECTION? |
| | PLEASE SEE 220.42 AND 220.43. |
| | |
| | 6) NOTE:PLEASE SEE PREVIOUS REVIEW NOTE #9. TRACK |
| | LIGHTING LOADS ARE STILL NOT SHOWN. |
| | PLEASE SEE NOTE #5 ABOVE IN WHICH SECTION 220.43 WAS |
| | BRIEFLY SATED FOR LOAD CALCULATIONS. PLEASE SHOW ALL |
| | TRACK LIGHTING LOADS AND HOW THEY ARE DERIVED. AS THESE |
| | ARE SPECIFIED AT THIS TIME COMPLIANCE CAN NOT BE |
| | VERIFIED. THIS WILL AFFECT THE DIMMER PANELS. |
| | |
| | 7) NOTE: PLEASE SEE PREVIOUS NOTE #10. PLEASE SEE THESE |
| | WERE NOT REVISED. TO MEET THE EXCEPTION IN THE CODE |
| | ONLY A SPECIFIC BREAKER MAY BE USED. A SNAP ON TYPE |
| | DEVICE IS NOT LISTED FOR PERMANENT INSTALLATION. PLEASE |
| | SEE 700.12F FOR CIRCUITING OF EMERGENCY LIGHTS. THESE |
| | SHALL BE CIRCUITED TO THE LOCAL BRANCH CIRCUIT IN ANY |
| | ONE AREA. |
| | |
| | 8) NOTE: PLEASE SEE NEW RISER AS TENANT IS NOW SHOWN |
| | BEING FED FROM TWO COMPLETELY SEPARATE SERVICES WHICH |
| | IS NOT PERMITTED. |
| | THERE ARE NO SEPARATE VOLTAGES ETC WHICH WOULD REQUIRE |
| | THE ELECTRICAL TO BE FED FROM SEPARATE SERVICES. THERE |
| | ARE NO OTHER EXCEPTIONS SHOWN TO JUSTIFY. |
| | PLEASE KNOW THE FIRE MARSHAL ALSO HAS CONCERN OVER |
| | MULTIPLE MAIN DISCONNECTS FOR ONE TENANT. NO SIGNAGE, |
| | NO NOTES, NO INFORMATION OF LABELING ETC IS SHOWN. AS |
| | NOTED ABOVE NO LOAD CALCULATIONS ETC WERE SUBMITTED. AS |
| | THIS IS NO COMPLETE AT THIS TIME THERE ARE MANY |
| | UNANSWERED QUESTIONS. |
| | 230, 240, 220 ET |
| | |
| | 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. PLEASE KNOW ONE |
| | SET OF ELECTRICAL PLANS HAVE BEEN RETAINED BY THIS |
| | OFFICE/REVIEWER. |
| | |
| | |
| | IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |