| Date |
Text |
| 2008-05-12 12:04:56 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING W/2007 REV |
| | FBC-2004 BUILDING W/2007 REV |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ALL SHEETS WITH ARCHITECTURAL TITLE BLOCK. THE |
| | ADDRESS OF RECORD ON THE FLORIDA STATE DBPR WEBSITE |
| | DOES NOT REFLECT THE ADDRESS ON THE TITLE BLOCKS FOR |
| | THE ARCHITECT. PLEASE CORRELATE THE ADDRESS ON THE |
| | TITLE BLOCK SO THAT IT RELFECTS THE ADDRESS OF RECORD |
| | WITH THE STATE. EITHER UPDATE THE DBPR WEBSITE OR THE |
| | TITLE BLOCKS PRIOR TO RESUBMITTING PLANS FOR REVIEW. |
| | FAC 61G1-16.004(1) & FS 481.219, 481.2055. |
| | |
| | 2. SHT A1.0 LIST OF DRAWINGS DOES NOT REFLECT THE |
| | SHEETS SUBMITTED. SHTS S-1, E-6, A-1, A-2 & A-3 WERE |
| | SUBMITTED BUT NOT SHOWN ON THE DRAWING LIST. ALSO SHTS |
| | FP-1, FS-2, FS-3 & FS-4 WERE INDICATED ON THE LIST BUT |
| | NOT SUBMITTED. PLEASE CORRELATE THE DRAWING LIST WITH |
| | SHEETS SUBMITTED. SECTION 106.1.3. |
| | |
| | 3. SHTS A2.0 & A4.0 DETAIL #1 ACCESSIBLE STALL SHALL |
| | COMPLY WITH FIGURE 11-30(E). THE LAV CAN NOT BE IN THE |
| | CLEAR FLOOR SPACE OF THE W/C AND THE W/C SHALL BE |
| | LOCATED IN THE CORNER, DIAGONAL TO THE DOOR. SECTION |
| | 11-4.17.3. |
| | |
| | 4. SHTS A2.0 & A4.0 SHOW COMPLIANCE WITH THE |
| | FOLLOWING: |
| | __FOR W/C: |
| | A. 11-4.16.5 FLUSH CONTROLS |
| | __FOR LAV: |
| | A. 11-4.19.2 CLEARANCES |
| | B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | |
| | 5. SUBMIT A DETAIL FOR THE ACCESSIBLE URINAL SHOWING |
| | COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS & |
| | FIGURES. |
| | |
| | 6. SHT A5.0 FINISH SCHEDULE. SHOW COMPLIANCE WITH |
| | SECTION 1210.2 REQUIREMENT FOR WALLS WITHIN 2FT OF |
| | W/C'S & URINALS TO BE A SMOOTH, HARD & NONABSORBENT |
| | SURFACE. THE SCHEDULE IS INDICATING PAINT WHICH DOES |
| | NOT COMPLY WITH THE "HARD" PORTION OF THE |
| | REQUIREMENTS. |
| | |
| | 7. SHTS P-1 & P-2 PLEASE INDICATE ON THE RISER AND |
| | SUBMIT A DETAIL FOR THE SAMPLE POINT REQUIRED ON THE |
| | GREASE LINE. THE SAMPLE POINT SHALL BE A 4" CROSS WITH |
| | A MINIMUM 12" DROP BELOW THE DRAIN LINE WITH A HARD CAP |
| | AND A CLEANOUT UP TO FINISHED FLOOR ABOVE THE DRAIN |
| | LINE. SECTION 106.1.2. |
| | |
| | 8. SHTS P-1 & P-2 TRAP PRIMERS ARE REQUIRED AT ALL |
| | FLOOR DRAINS WHERE THE TRAP IS SUBJECT TO LOSS BY |
| | EVAPORATION SUCH AS THE FLOOR DRAIN AT THE WATER |
| | HEATER. SECTION 1002.4. PLEASE SHOW ON THE RISER |
| | DIAGRAMS. |
| | |
| | 9. SHT P-1 INDICATES 2 FFD'S BUT NO CONNECTION TO THE |
| | SANITARY BUILDING DRAIN OR BRANCH LINE. PLEASE CLARIFY. |
| | ALL INDIRECT WASTE SHALL DRAIN INTO A FLOOR SINK OR A |
| | HUB DRAIN AS A FLOOR DRAIN IS NOT AN APPROVED INDIRECT |
| | WASTE RECEPTOR. SECTIONS 802.3 & 802.3.2. |
| | |
| | 10. SHT P-1 NO WATER SUPPLY IS SHOWN TO ITEMS 39, 40, |
| | 41, 42 & 56. THIS DOES NOT REFLECT SHT P-2 RISER |
| | DIAGRAM. PLEASE CORRELATE. SECTIONS 106.1.1, 601.1 & |
| | 604.3. |
| | |
| | 11. SHT P-2 WATER RISER DIAGRAM DOES NOT RELFLECT THE |
| | FLOOR PLAN. NO WATER IS SHOWN TO THE WALL HYDRANTS. |
| | PLEASE SHOW PIPING, PIPE SIZE, VALVES ETC.--ALSO |
| | THERE IS NO WATER SHOWN TO THE ICE MAKER. SECTIONS |
| | 106.1.1, 601.1 & 604.3. |
| | |
| | 12. SHT P-2 SANITARY RISER DIAGRAM. SAFE WASTES ARE NOT |
| | APPROVED. THE FFDS CONNECTING TO THE FLOOR SINK SHALL |
| | BE DELETED AND FLOOR SINKS SHALL BE INSTALLED OR THE |
| | INDIRECT PIPING SHALL BE INSTALLED TO THE FLOOR SINKS |
| | SHOWN. (SEE ITEMS 38, 39, 40, 60, 61 & 62).--ALSO |
| | FIXTURES SHALL NOT BE DOUBLE TRAPPED PER SECTION |
| | 1002.1. |
| | |
| | 13. SHT P-2 SANITARY RISER DIAGRAM DOES NOT REFLECT THE |
| | FLOOR PLAN UPSTREAM OF ITEMS 49 & 50 AS WELL AS |
| | DOWNSTREAM OF ITEM 45. PLEASE CORRELATE.--IDENTIFY |
| | THE FIXTURE UPSTREAM OF FFD FOR ITEM 54. ITEM 54 IS |
| | REQUIRED TO DRAIN INTO A FLOOR SINK OR A HUB DRAIN PER |
| | SECTIONS 803.2 & 803.2.3. |
| | |
| | 14. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING |
| | INFORMATION IS REQUIRED FOR PERMIT: |
| | |
| | A. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | B. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | |
| | C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | D. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | E. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | |
| | F. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | |
| | 15. SHT P-4 PLUMBING FIXTURE SCHEDULE INDICATES A |
| | CONCRETE LAV, BUT UNDER MANUFACTURE IT STATES "REFER TO |
| | ARCHITECTURAL DRAWINGS". SHT A4.0 DETAIL 1 REFERS TO |
| | NOTE "J" WHICH REFERS TO I.D. DRAWINGS WHICH WERE NOT |
| | SUBMITTED. PLEASE SUBMIT MANUF. SPECIFICATION SHEETS |
| | FOR THE LAV. PLEASE INDICATED MANUF & MODEL NUMBER. |
| | SECTION 303..4. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |