Plan Review Notes
Plan Review Notes For Permit 08040824
Permit Number 08040824
Review Stop P
Sequence Number 1
Notes
Date Text
2008-05-12 12:04:56DENIED
 REFERENCE: FBC-2004 PLUMBING W/2007 REV
 FBC-2004 BUILDING W/2007 REV
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS WITH ARCHITECTURAL TITLE BLOCK. THE
 ADDRESS OF RECORD ON THE FLORIDA STATE DBPR WEBSITE
 DOES NOT REFLECT THE ADDRESS ON THE TITLE BLOCKS FOR
 THE ARCHITECT. PLEASE CORRELATE THE ADDRESS ON THE
 TITLE BLOCK SO THAT IT RELFECTS THE ADDRESS OF RECORD
 WITH THE STATE. EITHER UPDATE THE DBPR WEBSITE OR THE
 TITLE BLOCKS PRIOR TO RESUBMITTING PLANS FOR REVIEW.
 FAC 61G1-16.004(1) & FS 481.219, 481.2055.
  
 2. SHT A1.0 LIST OF DRAWINGS DOES NOT REFLECT THE
 SHEETS SUBMITTED. SHTS S-1, E-6, A-1, A-2 & A-3 WERE
 SUBMITTED BUT NOT SHOWN ON THE DRAWING LIST. ALSO SHTS
 FP-1, FS-2, FS-3 & FS-4 WERE INDICATED ON THE LIST BUT
 NOT SUBMITTED. PLEASE CORRELATE THE DRAWING LIST WITH
 SHEETS SUBMITTED. SECTION 106.1.3.
  
 3. SHTS A2.0 & A4.0 DETAIL #1 ACCESSIBLE STALL SHALL
 COMPLY WITH FIGURE 11-30(E). THE LAV CAN NOT BE IN THE
 CLEAR FLOOR SPACE OF THE W/C AND THE W/C SHALL BE
 LOCATED IN THE CORNER, DIAGONAL TO THE DOOR. SECTION
 11-4.17.3.
  
 4. SHTS A2.0 & A4.0 SHOW COMPLIANCE WITH THE
 FOLLOWING:
 __FOR W/C:
 A. 11-4.16.5 FLUSH CONTROLS
 __FOR LAV:
 A. 11-4.19.2 CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
  
 5. SUBMIT A DETAIL FOR THE ACCESSIBLE URINAL SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS &
 FIGURES.
  
 6. SHT A5.0 FINISH SCHEDULE. SHOW COMPLIANCE WITH
 SECTION 1210.2 REQUIREMENT FOR WALLS WITHIN 2FT OF
 W/C'S & URINALS TO BE A SMOOTH, HARD & NONABSORBENT
 SURFACE. THE SCHEDULE IS INDICATING PAINT WHICH DOES
 NOT COMPLY WITH THE "HARD" PORTION OF THE
 REQUIREMENTS.
  
 7. SHTS P-1 & P-2 PLEASE INDICATE ON THE RISER AND
 SUBMIT A DETAIL FOR THE SAMPLE POINT REQUIRED ON THE
 GREASE LINE. THE SAMPLE POINT SHALL BE A 4" CROSS WITH
 A MINIMUM 12" DROP BELOW THE DRAIN LINE WITH A HARD CAP
 AND A CLEANOUT UP TO FINISHED FLOOR ABOVE THE DRAIN
 LINE. SECTION 106.1.2.
  
 8. SHTS P-1 & P-2 TRAP PRIMERS ARE REQUIRED AT ALL
 FLOOR DRAINS WHERE THE TRAP IS SUBJECT TO LOSS BY
 EVAPORATION SUCH AS THE FLOOR DRAIN AT THE WATER
 HEATER. SECTION 1002.4. PLEASE SHOW ON THE RISER
 DIAGRAMS.
  
 9. SHT P-1 INDICATES 2 FFD'S BUT NO CONNECTION TO THE
 SANITARY BUILDING DRAIN OR BRANCH LINE. PLEASE CLARIFY.
 ALL INDIRECT WASTE SHALL DRAIN INTO A FLOOR SINK OR A
 HUB DRAIN AS A FLOOR DRAIN IS NOT AN APPROVED INDIRECT
 WASTE RECEPTOR. SECTIONS 802.3 & 802.3.2.
  
 10. SHT P-1 NO WATER SUPPLY IS SHOWN TO ITEMS 39, 40,
 41, 42 & 56. THIS DOES NOT REFLECT SHT P-2 RISER
 DIAGRAM. PLEASE CORRELATE. SECTIONS 106.1.1, 601.1 &
 604.3.
  
 11. SHT P-2 WATER RISER DIAGRAM DOES NOT RELFLECT THE
 FLOOR PLAN. NO WATER IS SHOWN TO THE WALL HYDRANTS.
 PLEASE SHOW PIPING, PIPE SIZE, VALVES ETC.--ALSO
 THERE IS NO WATER SHOWN TO THE ICE MAKER. SECTIONS
 106.1.1, 601.1 & 604.3.
  
 12. SHT P-2 SANITARY RISER DIAGRAM. SAFE WASTES ARE NOT
 APPROVED. THE FFDS CONNECTING TO THE FLOOR SINK SHALL
 BE DELETED AND FLOOR SINKS SHALL BE INSTALLED OR THE
 INDIRECT PIPING SHALL BE INSTALLED TO THE FLOOR SINKS
 SHOWN. (SEE ITEMS 38, 39, 40, 60, 61 & 62).--ALSO
 FIXTURES SHALL NOT BE DOUBLE TRAPPED PER SECTION
 1002.1.
  
 13. SHT P-2 SANITARY RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN UPSTREAM OF ITEMS 49 & 50 AS WELL AS
 DOWNSTREAM OF ITEM 45. PLEASE CORRELATE.--IDENTIFY
 THE FIXTURE UPSTREAM OF FFD FOR ITEM 54. ITEM 54 IS
 REQUIRED TO DRAIN INTO A FLOOR SINK OR A HUB DRAIN PER
 SECTIONS 803.2 & 803.2.3.
  
 14. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR PERMIT:
  
 A. TYPE OF GAS, (LP OR NATURAL).
  
 B. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 D. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 E. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 F. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 15. SHT P-4 PLUMBING FIXTURE SCHEDULE INDICATES A
 CONCRETE LAV, BUT UNDER MANUFACTURE IT STATES "REFER TO
 ARCHITECTURAL DRAWINGS". SHT A4.0 DETAIL 1 REFERS TO
 NOTE "J" WHICH REFERS TO I.D. DRAWINGS WHICH WERE NOT
 SUBMITTED. PLEASE SUBMIT MANUF. SPECIFICATION SHEETS
 FOR THE LAV. PLEASE INDICATED MANUF & MODEL NUMBER.
 SECTION 303..4.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved