Plan Review Notes
Plan Review Notes For Permit 08040824
Permit Number 08040824
Review Stop M
Sequence Number 1
Notes
Date Text
2008-05-14 12:27:15PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLAN M-1 GENERAL HVAC NOTE 4.1 AND M-2 EQUIPMENT
 STAND DETAIL NOTE 2, REFERENCES HURRICANE FORCE WINDS.
 NEEDS TO STATE 140 MPH HURRICANE FORCE WINDS, PER 2004
 FBC 1609.
  
 2) PLAN M-2 IF CONDENSER STANDS ARE PRE-ENGINEERED
 PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR
 PER-ENGINEERED CONDENSER STANDS, SEE FS 553.842(1) AND
 FAC RULE 9B-72, 9B-72.005, AND FAC 9B-72.010(31)(G).
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 3) THE COOLING LOAD CALCULATIONS NEED TO BE SIGNED AND
 SEALED BY THE ENGINEER, PER 2004 FBC 13-407.1.ABC.1
 EXCEPT.
  
 4) WHEN RE-SUBMITTING THE ENERGY CALCULATIONS HAVE THEM
 SIGNED BY OWNER/AGENT ALSO, PER 2004 FBC 13-103.3. (SEE
 ELECTRICAL REVIEW NOTE 4 REGARDING E-CAL'S, PLEASE
 CORRECT).
  
 5)A/C SYSTEM MODEL NUMBERS LISTED ON THE A/C
 EQUIPMENT SCHEDULE COULD NOT BE FOUND ON THE ARI
 DIRECTORY WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI
 CERTIFICATE, PER 2004 FBC 13-407.1.ABC.3.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]