| 2008-05-27 12:30:15 | *****DENIED***** |
| | |
| | 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 02.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE |
| | WITH EMERGENCY RESPONSE TO THE SAID PROPERTY OR THE |
| | VICINITY THEREOF (INCLUDING STREETS, ALLEYS, FIRE |
| | LANES, ETC.). |
| | |
| | 03.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| | REFERENCED. |
| | |
| | 04.SINCE THE TOTAL OCCUPANT LOAD LISTED ON SHEET A1.0 |
| | IS 172 PEOPLE, VERIFY THAT THE DOOR(S) IN THE REQUIRED |
| | MEANS OF EGRESS FROM AN AREA HAVING AN OCCUPANT LOAD OF |
| | 100 OR MORE PERSONS SHALL BE PROVIDED WITH PANIC |
| | HARDWARE OR FIRE EXIT HARDWARE. |
| | |
| | 05.THE NUMBER OF EXIT LIGHTS SHOWN ON SHEET A2.1 DO |
| | NOT CORRELATE WITH THAT OF SHEET E-4. |
| | |
| | 06.THE FLOOR PLAN LEGEND ON SHEET A2.0 MAKES |
| | REFERENCE TO DOOR SCHEDULE ON SHEET A6.HOWEVER, A |
| | DOOR SCHEDULE ON SHEET A6 COULD NOT BE FOUND. |
| | |
| | 07.IT APPEARS ON SHEET A2.0 THAT THE JANITOR'S CLOSET |
| | DOOR (#10) OPENS IN THE PATH OF AN AISLE CORRIDOR MORE |
| | THAN ONE HALF THE WIDTH OF THE AISLE.PLEASE EXPLAIN. |
| | |
| | 08.ON SHEET A4.2, DISPLAY/SHOW THE NUMERICAL ADDRESS |
| | AT THE BUILDING'S FRONT ELEVATION.AS PER WEST PALM |
| | BEACH CODE, THE NUMBERS SHALL BE NO LESS THAN 6" IN |
| | HEIGHT AND NO LESS THAN 1" IN WIDTH/STROKE. |
| | |
| | 09.IT IS STATED THAT ON SHEET A5.0 THAT INTERIOR |
| | FINISHES SHALL COMPLY WITH NFPA 101 - 38.3.3;HOWEVER |
| | THIS SECTION OF NFPA DEALS WITH NEW BUSINESS |
| | OCCUPANCIES. |
| | |
| | 10.DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE |
| | ALARM.AMEND THE FIRE ALARM SYSTEM'S SEQUENCE OF |
| | OPERATION ON SHEET E-6 TO REFLECT THIS AHJ |
| | REQUIREMENT. |
| | |
| | 11.NFPA 72 - 2002 EDITION SHALL BE REFERENCED. PLEASE |
| | BE ADVISED THAT THE 1999 EDITION IS LISTED IN B UNDER |
| | THE FIRE ALARM SYSTEM SCOPE ON SHEET E-6. |
| | |
| | 12.SHOW THE LOCATION OF THE WATER FLOW DEVICE AND THE |
| | TAMPER SWITCH FOR THE FIRE ALARM/FIRE SPRINKLER |
| | SYSTEM. |
| | |
| | 13.IN REFERENCE TO THE FIRE SPRINKLER SYSTEM, NFPA 13 |
| | - 2002 EDITION SHALL BE REFERENCED. |
| | |
| | 14.THE SUBMITTED PLAN SHEETS DO NOT ACTUALLY |
| | CORRELATE WITH THE LIST OF DRAWINGS AS SHOWN SO SHEET |
| | A1.0 |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESWS, INCLUDE A |
| | RESPONSE LETTER INDICATING WHERE ON THE APPROPIATE PLAN |
| | SHEET EACH ITEM WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |