2008-05-27 12:30:15*****DENIED*****
  
 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 02.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY RESPONSE TO THE SAID PROPERTY OR THE
 VICINITY THEREOF (INCLUDING STREETS, ALLEYS, FIRE
 LANES, ETC.).
  
 03.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 04.SINCE THE TOTAL OCCUPANT LOAD LISTED ON SHEET A1.0
 IS 172 PEOPLE, VERIFY THAT THE DOOR(S) IN THE REQUIRED
 MEANS OF EGRESS FROM AN AREA HAVING AN OCCUPANT LOAD OF
 100 OR MORE PERSONS SHALL BE PROVIDED WITH PANIC
 HARDWARE OR FIRE EXIT HARDWARE.
  
 05.THE NUMBER OF EXIT LIGHTS SHOWN ON SHEET A2.1 DO
 NOT CORRELATE WITH THAT OF SHEET E-4.
  
 06.THE FLOOR PLAN LEGEND ON SHEET A2.0 MAKES
 REFERENCE TO DOOR SCHEDULE ON SHEET A6.HOWEVER, A
 DOOR SCHEDULE ON SHEET A6 COULD NOT BE FOUND.
  
 07.IT APPEARS ON SHEET A2.0 THAT THE JANITOR'S CLOSET
 DOOR (#10) OPENS IN THE PATH OF AN AISLE CORRIDOR MORE
 THAN ONE HALF THE WIDTH OF THE AISLE.PLEASE EXPLAIN.
  
 08.ON SHEET A4.2, DISPLAY/SHOW THE NUMERICAL ADDRESS
 AT THE BUILDING'S FRONT ELEVATION.AS PER WEST PALM
 BEACH CODE, THE NUMBERS SHALL BE NO LESS THAN 6" IN
 HEIGHT AND NO LESS THAN 1" IN WIDTH/STROKE.
  
 09.IT IS STATED THAT ON SHEET A5.0 THAT INTERIOR
 FINISHES SHALL COMPLY WITH NFPA 101 - 38.3.3;HOWEVER
 THIS SECTION OF NFPA DEALS WITH NEW BUSINESS
 OCCUPANCIES.
  
 10.DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM.AMEND THE FIRE ALARM SYSTEM'S SEQUENCE OF
 OPERATION ON SHEET E-6 TO REFLECT THIS AHJ
 REQUIREMENT.
  
 11.NFPA 72 - 2002 EDITION SHALL BE REFERENCED. PLEASE
 BE ADVISED THAT THE 1999 EDITION IS LISTED IN B UNDER
 THE FIRE ALARM SYSTEM SCOPE ON SHEET E-6.
  
 12.SHOW THE LOCATION OF THE WATER FLOW DEVICE AND THE
 TAMPER SWITCH FOR THE FIRE ALARM/FIRE SPRINKLER
 SYSTEM.
  
 13.IN REFERENCE TO THE FIRE SPRINKLER SYSTEM, NFPA 13
 - 2002 EDITION SHALL BE REFERENCED.
  
 14.THE SUBMITTED PLAN SHEETS DO NOT ACTUALLY
 CORRELATE WITH THE LIST OF DRAWINGS AS SHOWN SO SHEET
 A1.0
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESWS, INCLUDE A
 RESPONSE LETTER INDICATING WHERE ON THE APPROPIATE PLAN
 SHEET EACH ITEM WAS ADDRESSED
  
  