Plan Review Notes
Plan Review Notes For Permit 08040824
Permit Number 08040824
Review Stop E
Sequence Number 1
Notes
Date Text
2008-05-05 07:43:26** DENIED**
  
 *** PLEASE KNOW IT IS IMPORTANT TO KNOW THERE ARE
 SEVERAL ITEMS NOT YET SUBMITTED FOR CODE COMPLIANCE IN
 DESIGN. IT IS IMPORTANT TO UNDERSTAND THERE MAY VERY
 WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN
 NOT BE MADE AT THIS TIME.
  
  
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES AT A
 MINIMUM FOR THE REVIEWER ARE STATED ON ELECTRICAL PLANS
 AS WELL AS COVER SHEET.
  
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 ** SOME CODES ARE ALREADY STATED HOWEVER NOT ALL
 RELEVANT AS STATED ABOVE. THIS IS ONLY FOR ELECTRICAL
 REVIEW AND OTHER CODES FROM OTHER TRADES MAY CERTAINLY
 BE REQUIRED.
  
 2) NOTE: PLEASE SEE FIRE REVIEW AND BUILDING REVIEW
 COMMENTS AS THIS BUILDING IS CONSIDERED MORE THAN THREE
 STORIES.
 SHEET A1.0 CLEARLY STATES THIS IS A *2-STORY* BUILDING
 HOWEVER THIS IS NOT THE CASE. THE BUILDING BY
 DEFINITION IS AT MINIMUM 4-STORY. PLEASE SEE COMMENTS
 FROM BUILDING REVIEW.
 FOR INFORMATION: THE ORIGINAL FIRE WALLS WHICH USED TO
 SEPARATE PARTS OF THIS STRUCTURE ARE NO LONGER FIRE
 WALLS BY DEFINITION.
  
 3) NOTE: PLEASE SEE SOME LOCATIONS ARE MISSING
 HORN/STROBE FOR ADA COMPLIANCE PER FBC 11-4.28.1, .2 AN
 D.3(4).
 PLEASE SEE ONE LOCATION FOR EXAMPLE IS THE BATHROOMS.
 NOTE #9 ON PLANS MENTIONS TO INSTALL NEW DEVICES TO
 MATCH EXISTING. IT IS NOT POSSIBLE TO MATCH EXISTING
 WHEN THERE ARE NOT EXISTING DEVICES. THIS SPACE HAS
 BEEN COMPLETELY GUTTED.
 PLEASE SHOW DEVICES FOR COMPLIANCE.
  
 4) NOTE: PLEASE SEE THE SUBMITTED METHOD *A* ENERGY
 CALCULATIONS MAY NOT BE USED. THIS IS FOR A TENANT
 BUILD OUT ONLY, THIS IS NOT FOR A WHOLE BUILDING.
 PLEASE SEE THE DEFINITIONS. METHOD *A* MAY BE USED ON
 ADDITIONS AND WHOLE BUILDINGS OR WHEN *ALL BUILDING
 COMPONENTS* ARE KNOWN. THIS SCENARIO AS SUBMITTED WOULD
 NOT FALL UNDER THIS CRITERIA.
 PLEASE SEE 13-101.1.1, 13-101.1.2,13-101.3,
 13-400.0.A,13-400.0.B, 13-400.0.C,ETC.
 PLEASE SEE MECHANICAL REVIEW COMMENTS WITH RESPECT TO
 MINIMUM REQUIREMENTS REQUIRED.
 THIS COMMENT IS GIVEN FOR INFORMATION FOR ALL OTHER
 TRADES HOWEVER ELECTRICAL COMPLIANCE WITH SECTIONS
 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3 NEED TO BE
 MET.
 AS THE CALCULATIONS SUBMITTED ARE NOT VALID PLEASE
 SUBMIT COMPLETE LIGHTING PERFORMANCE CALCULATIONS UNDER
 METHOD PERMITTED.
 PLEASE CALL TO GO OVER THIS.
 PLEASE SEE THE INFORMATION ON THE INPUT DATA REPORTS IS
 REQUIRED TO COORDINATE WITH PLANS COMPLETELY.
  
 A) PLEASE SEE ONE EXAMPLE IS THAT THE METHOD OF
 CONTROLS FOR LIGHTING IS SHOWN AS *MANUAL ON/OFF*. HOW
 IS THIS POSSIBLE WHEN ALL LIGHTING IS REQUIRED TO
 CONTAIN AUTOMATED CONTROLS?
 PLEASE SEE THE FOLLOWING COMMENT WITH RESPECT TO
 LIGHTING CONTROLS.
  
 B) PLEASE SEE ANOTHER EXAMPLE OF ITEMS ON THE IDR WHICH
 DO NOT COORDINATE WITH PLANS IS THE NUMBER OF LIGHT
 FIXTURES SHOWN. PLEASE SEE THE TOTAL NUMBER OF FIXTURES
 SHOWN ON THE IDR FOR INTERIOR IS *8*. THIS IS NOT
 POSSIBLE WHEN THERE IS CLEARLY DOZENS OF FIXTURES ON
 PLANS.
  
 C) PLEASE SEE ANOTHER EXAMPLE OF ITEMS ON PLANS WHICH
 DO NOT COORDINATE WITH THE IDR IS THE EXTERIOR
 FIXTURES. PLEASE SEE THIS IS ACTUALLY BLANK ON THE IDR
 YET THERE ARE CLEARLY EXTERIOR LIGHT FIXTURES ON PLANS.
 PLEASE SEE 13-415.2.ABC.1.3 AS NOTED ABOVE FOR EXTERIOR
 LIGHTING PERFORMANCE.
  
 D) PLEASE BE SURE TO SEE THE SECTIONS OF CODE AS NOTED
 ABOVE SPECIFICALLY FOR TRACK LIGHTING.
 BASED ON THE PLANS THE FIXTURE LEGEND IS NOT COMPLETE.
 ALL FIXTURES MUST BE LABELED. ALL FIXTURES MUST BE
 FIGURED INTO THE PERFORMANCE CALCULATIONS OF SPACE.
  
 ** IMPORTANT**
 THESE EXAMPLES ABOVE ARE NOT IN ANYWAY AN EXHAUSTED
 LIST OF ALL ITEMS ON PLANS WHICH DO NOT COORDINATE WITH
 THE SUBMITTED CALCULATIONS. THESE ARE GIVEN AS A
 BENEFIT ONLY AS CODE COMPLIANCE HAS NOT BEEN ACHIEVED.
 PLEASE BE SURE TO GO OVER COMMENTS AND COORDINATE ALL.
  
  
 5) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND
 .1.4.
  
 A) PLEASE VERIFY ALL OVER RIDE LOCATIONS REQUIRED.
 PLEASE SEE THAT AN OCCUPANT MUST BE ABLE TO OVER RIDE
 ANY TIME OF DAY SCHEDULING AT THE POINT OF ENTRANCE
 INTO ANY ONE SPACE. THE OCCUPANT MUST BE ABLE TO SEE
 ALL LIGHTING WHICH IS BEING CONTROLLED OR NEEDS TO MEET
 EXCEPTIONS.
  
 B) PLEASE SEE SOME LIGHTING CONTROLS SHOWN ON PLANS ARE
 STANDARD SWITCHES. HOW IS THIS POSSIBLE WHEN AUTOMATED
 CONTROLS ARE REQUIRED?
 SOME LOCATION EXAMPLES ARE HALL, ACCENT LIGHTS, LIQUOR
 STORAGE, CLOSET ETC
 ** THIS IS NOT ALL LOCATIONS AS THERE ARE OTHERS. ONLY
 SOME ARE GIVEN AS EXAMPLES.
  
 C) PLEASE SEE PLANS ARE MISSING REQUIRED SEPARATE SPACE
 CONTROLS. THESE ARE REQUIRED TO BE AUTOMATED OR PART OF
 A SYSTEM WITH OVER RIDES.
  
 D) PLEASE PROVIDE A COMPLETE SYSTEM/ETC FOR MINIMUM
 LIGHTING CONTROLS AS REQUIRED PER SECTIONS ABOVE.
 PLEASE PROVIDE COMPLETE SCHEDULE OF SYSTEM, SCHEDULE
 FOR ALL ITEMS ON THE DIMMING PANEL.
 AS NO SCHEDULE WAS SUBMITTED THERE ARE SEVERAL ITEMS
 WHICH CAN NOT BE DETERMINED FOR CODE COMPLIANCE WITH
 REQUIRED LIGHTING CONTROLS AS WELL AS OTHER COMMENTS.
 PLEASE SEE THE FOLLOWING COMMENT.
 PLEASE KNOW COMPLETE COMPLIANCE FOR AUTOMATED LIGHTING
 CONTROLS IS REQUIRED.THIS IS A BUILDING OVER 5000 SQ
 FT.
  
 E) PLEASE SEE SECTION 13-415.1.ABC.1.4 FOR EXTERIOR
 LIGHTING CONTROLS. PLANS SHOW THESE EXTERIOR LIGHTS
 THROUGH DIMMING PANEL. PLEASE SEE THE SECTION OF CODE
 WHICH PERMITS TWO METHODS.
  
  
 ** IT IS IMPORTANT TO KNOW AS NO LIGHTING CONTROL
 SYSTEM, OR DEVICES WERE SUBMITTED AS PART OF THE DESIGN
 THESE SPECIFIC ITEMS COULD NOT BE REVIEWED. CODE
 COMPLIANCE WAS REQUIRED TO BE ON DESIGN FOR INITIAL
 REVIEW. THERE MAY BE NEW COMMENTS ON THE FOLLOWING
 REVIEW WHICH COULD NOT BE MADE AT THIS TIME.
  
 6) NOTE: PLEASE KNOW AS PLANS CLEARLY INDICATE NORMAL
 LIGHTING BEING CONTROLLED THROUGH A DIMMING PANEL OF
 SOME KIND PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR
 EGRESS PATHS FOR MINIMUM LIGHTING LEVELS.
 PLEASE KNOW THE MINIMUM LEVELS FOR LIGHTING SHALL NOT
 BE PERMITTED TO DIM BELOW THE 1FT CANDLE REQUIRED BY
 THE LIFE SAFETY CODE, NFPA-101 7.8, 7.9.
 PLEASE PROVIDE MORE INFORMATION.
 FBC 106.1.2.
 FAC 61G15-33.004
  
 7) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS ON
 THE EXISTING 1000AMP MAIN IN WHICH THE NEW 600AMP MAIN
 IS BEING ADDED.
 PLEASE OBTAIN ALL RECENT LOADS WHICH HAVE BEEN ADDED TO
 BUILDING AND POSSIBLY THIS SERVICE.
 PLEASE SEE 220.87. A LOAD STUDY MAY NOT BE ACCURATE AS
 NEW LOADS HAVE CONTINUALLY BEEN ADDED AND SOME LOADS
 HAVE NOT BEEN COMPLETED ON SERVICE.
 PLEASE SEE CODES REFLECTED ON THE CALCULATIONS NEED TO
 COORDINATE WITH CODE. PLEASE VERIFY 220.44 AS NOTED FOR
 ALL OTHER LOADS. HOW ARE LIGHTING LOADS UNDER THIS SAME
 CODE SECTION?
 PLEASE SEE 220.42 AND 220.43.
  
 8) NOTE: PLEASE VERIFY HOW THE LOADS ON THE LIGHTING
 DIMMING PANELS ARE SHOWN EXCEEDING THE RATING OF THE
 FEEDER.
 PLEASE SHOW ALL CONTINUOUS LOADS AT 125%.215.3, 230.42
 ETC PLEASE KNOW THIS WILL AFFECT OTHER LOADS ON PANELS,
 SERVICE ETC. PLEASE BE SURE TO FOLLOW THROUGH WITH
 SERVICE.
  
 9) NOTE: PLEASE SEE NOTE #7 ABOVE IN WHICH SECTION
 220.43 WAS BRIEFLY SATED FOR LOAD CALCULATIONS. PLEASE
 SHOW ALL TRACK LIGHTING LOADS AND HOW THEY ARE DERIVED.
 AS THESE ARE SPECIFIED AT THIS TIME COMPLIANCE CAN NOT
 BE VERIFIED. THIS WILL AFFECT THE DIMMER PANELS.
  
 10) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF
 EMERGENCY LIGHTS. THESE SHALL BE CIRCUITED TO THE LOCAL
 BRANCH CIRCUIT IN ANY ONE AREA.
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]