Plan Review Notes
Plan Review Notes For Permit 08040822
Permit Number 08040822
Review Stop Z
Sequence Number 2
Notes
Date Text
2008-06-03 10:21:00***FAILED - RESUB #1***
  
  
 1)THE SURVEY AND SITE PLAN (SHEET 1) DO NOT MATCH
 WITH RESPECT TO THE EXISTING AND PROPOSED SETBACK
 DIMENSIONS.PLEASE CLARIFY.THE SIDE SETBACKS AS
 SHOWN ON THE SURVEY DO NOT MEET THE MINIMUM REQUIRED BY
 SECTION 94-72 OF THE CITY'S ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDRS):SIDE = 5' MINIMUM WITH A TOTAL OF
 15' BETWEEN THE TWO SIDES, THE SURVEY SHOWS A TOTAL OF
 14.8'.PLEASE REVISE, ALL PLANS SHALL
 CORRESPOND/MATCH.
  
 2)AS THE VALUE OF THE WORK HAS INCREASED TO
 ACCURATELY REFLECT THE SCOPE OF WORK, IT NOW TRIGGERS
 SECTION 94-441(C)(2) OF THE ZLDRS: AS THE VALUE OF THE
 PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDRS.PLEASE SUBMIT A LANDSCAPE PLAN SHOWING
 COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF THE
 ZLDRS.
  
 3)THE POOL EQUIPMENT AS SHOWN ON THE SURVEY MUST BE A
 MINIMUM OF 4.1 FEET FROM THE SOUTH SIDE PROPERTY LINE.
 AS PER SECTION 94-305(B)(4) OF THE ZLDRS: MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A
 REQUIRED SETBACK.PLEASE REVISE.
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "M" - TG