| 2008-06-03 12:02:39 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) ENERGY CALCULATIONS LINE 11A IS STATING THE SUPPLY |
| | AND RETURN AIR DUCTS ARE IN A CONDITIONED SPACE, AND |
| | THE AIR HANDLER IS IN THE INTERIOR. THE MECHANICAL |
| | PLANS SHOW THE SUPPLY AIR DUSTS ARE IN THE ATTIC, SHOWS |
| | NO RETURN AIR DUCTS, AND SHOWS THE AIR HANDLER IN THE |
| | ATTIC. PLEASE CORRECT THE ENERGY CALCULATIONS, PER 2004 |
| | FBC 13-600.3.A. |
| | |
| | 2) WHEN RESUBMITTING THE ENERGY CALCULATIONS THEY MUST |
| | BE SIGNED BY OWNER/AGENT ALSO, PER 2004 FBC 13-103.3. |
| | |
| | 3) THE COOLING LOAD CALCULATIONS ARE CALLING FOR 27,626 |
| | TOTAL BTU'S, AND THE MECHANICAL PLAN EQUIPMENT LISTING |
| | IS SHOWING 41,200 TOTAL BTU'S. THE PLANS CAN ONLY CALL |
| | FOR 15% MORE TOTAL BTU'S THAN THE COOLING LOAD CAL'S. |
| | PER 2004 FBC 13-607.1.ABC.1.1, PLEASE CORRECT. |
| | |
| | 4)A/C SYSTEM MODEL NUMBERS LISTED ON THE A/C |
| | EQUIPMENT SCHEDULE A/H FKYCNB005 AND C/U 38BRL042-3 |
| | COULD NOT BE FOUND ON THE ARI DIRECTORY WEB-SITE, |
| | PLEASE CORRECT OR SUBMIT AN ARI CERTIFICATE, SEE 2004 |
| | FBC 13-607.1.ABC.3.1.1. |
| | |
| | 5) THE PLAN SHOWS NO A/C GOING TO THE PROPOSED BEDROOM |
| | PLEASE CORRECT OR STATE NO A/C THIS ROOM ON PLAN. |
| | |
| | 6) PLANS SHOW NO RETURN AIR TO AIR HANDLER PLEASE SHOW |
| | ON PLAN HOW THE AIR IS RETURNING TO THE AIR HANDLER, |
| | PER 2004 FBC/R M1602.4. |
| | |
| | 7) PLEASE PROVIDE FOR RETURN AIR TO THE PROPOSED STUDY |
| | AND PROPOSED BEDROOM (IF A/C), PER 2004 FBC/R M1602.4. |
| | |
| | 8) PLEASE SHOW THE ATTIC ACCESS TO THE AIR HANDLER ON |
| | MECHANICAL PLAN, PER 2004 FBC/R M1305.1.3. |
| | |
| | 9) THE MECHANICAL PLANS NEED THE PRINTED NAME WITH THE |
| | SINGATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN, AND |
| | CONTRACTOR INFORMATION IF APPLICABLE ON THEM, SEE |
| | W.P.B. AMEND. 106.1.3. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729 |
| | E-MAIL; [email protected] |