Plan Review Notes
Plan Review Notes For Permit 08040822
Permit Number 08040822
Review Stop B
Sequence Number 2
Notes
Date Text
2008-06-05 13:54:552004 FBC W/2007 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) PLEASE SUBMIT A COPY OF THE PAID RECEIPT FOR THE
 COUNTY IMPACT FEES.
  
 2) THE ENERGY CALCULATION FORMS ARE REQUIRED TO BE
 SIGNED BY THE OWNER/AGENT. SEE FBC 13-600.
  
 3) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES LISTED
 IN THE NOA FOR THE MODIFIED ROOFING WILL BE INSTALLED.
 SPECIFY THE FASTENING OPTION AND DESIGN PRESSURE THAT
 WILL BE USED. SUBMIT RAS 117 CALCULATIONS FOR THE
 ENHANCED FASTENING OF THE BASE SHEET AT PERIMETER AND
 CORNERS. SEE LIMITATION #7 ON PAGE 32 OF THE NOA. PAGE
 28 OF THE NOA IS FOR TORCH DOWN APP/SBS FOR
 NON-INSULATED WOOD DECKS. SOME PAGES ARE MISSING FROM
 THE NOA THAT WAS SUBMITTED. THE ROOFING CONTRACTOR CAN
 PROVIDE THIS INFORMATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW