| Date |
Text |
| 2008-05-02 11:19:35 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET A-1.0 SANITARY RISER DIAGRAM: PER FBC-2004 |
| | PLUMBING SECTION 406.3 WASTE CONNECTIONS. THE AUTOMATIC |
| | CLOTHES WASHER FIXTURE DRAIN SHALL CONNECT TO A BRANCH |
| | DRAIN OR DRAINAGE STACK A MINIMUM OF 3 INCHES (76MM) IN |
| | DIAMETER. |
| | |
| | 2. SHEET A-1.0 SANITARY RISER DIAGRAM: BATHROOM #2 |
| | DOES NOT REFLECT THE FLOOR PLAN ON SHEET A-2.0. THE |
| | FLOOR PLAN ON SHEET A-2.0 INDICATES ONE SHOWER FOR THIS |
| | BATHROOM HOWEVER THE ISOMETRIC ON SHEET A-1.0 IS |
| | INDICATING TWO SHOWERS. ALSO THE LAVATORY TRAP ON SHEET |
| | A-1.0 ISOMETRIC IS BEING INDICATED IN THE WRONG ROOM. |
| | PLEASE CORRECT THE ISOMETRIC ON SHEET A-1.0 FOR |
| | BATHROOM #2 TO REFLECT THE FLOOR PLAN ON SHEET A-2.0. |
| | PER FBC-2004 PLUMBING SECTION 701.1 SCOPE. |
| | |
| | 3. SHEET A-2.0 FLOOR PLAN GARAGE: PLEASE PROVIDE A |
| | DETAIL ON HOW THE GAS WATER HEATER WILL BE PROTECTED |
| | FROM PHISICAL DAMAGE FROM VEHICLE IMPACT. PER FBC-2004 |
| | FUEL GAS SECTION 303.4 PROTECTION FROM PHYSICAL |
| | DAMAGE. |
| | |
| | 4. SHEET D-2PLUMBING NOTES: STATES THE FOLLOWING |
| | "MINIMUM SLOPE SHALL BE 1/8" PER FOOT". PLEASE CLEARLY |
| | INDICATE THE MINIMUM SLOPE OF HORIZONTAL DRAINAGE |
| | PIPING SHALL BE PER FBC-2004 W/07 REVISIONS PLUMBING |
| | TABLE 704.1. 2-1/2" OR LESS SHALL BE 1/4" PER FOOT |
| | SLOPE, 3" TO 6" SHALL BE 1/8" PER FOOT SLOPE AND 8" OR |
| | LARGER SHALL BE 1/16" PER FOOT SLOPE. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |