| 2008-05-06 17:37:51 | 2004 FBC W/2007 REVISIONS |
| | NEW SINGLE FAMILY DWELLING |
| | |
| | DENIED BY BUILDING |
| | |
| | 1)FBC R401.4AREA OF QUESTIONABLE |
| | SOIL.SUBMIT A GEOTECHNICAL REPORT |
| | TO VERIFY THE SAFE BEARING CAPACITY OF |
| | THE SOIL. |
| | |
| | 2) THE NAIL SIZE FOR ROOF SHEATHING SPECIFIED IN THE |
| | SCHEDULE ON SHEET D-1 IS FOR AN 8D COMMON NAIL. THE |
| | PLANS SPECIFY 10D NAILS ON A-5.0. FBC R803.2.3.1 OF |
| | 2006 REVISIONS TO 2004 FBC RESIDENTIAL CODE REQUIRES 8D |
| | RING-SHANK NAILS. |
| | |
| | 3) THE TYPICAL WALL SECTION ON D-1 SHOWS AN 18" X 16" |
| | FOOTING AND THE SCHEDULE ON A-1.0 SPECIFIES A 16" X 16" |
| | FOOTING. PLEASE CLARIFY. FBC 106.1.1* CITY AMENDMENTS |
| | |
| | 4)THE NAILING SCHEDULE FOR PNEUMATIC FASTENERS ON |
| | SPECIFIES A SPACING OF 16" OC FOR DOOR AND GARAGE DOOR |
| | BUCKS. DETAIL 8 ON D-1 AND 2 ON D-2 SPECIFY 12" OC. |
| | PLEASE CORRECT. FBC 106.1.1* CITY AMENDMENTS |
| | |
| | 5) NOTE: SOME OF THE FASTENERS LISTED IN THE SCHEDULE |
| | ARE NOT PNEUMATIC FASTENERS. |
| | |
| | 6) SUBMIT THE LISTING INFORMATION FOR THE ONE HOUR FIRE |
| | RATED GLASS BLOCK SYSTEM THAT IS REQUIRED ON THE ZERO |
| | LOT LINE. THE PRODUCT APPROVAL SUBMITTED IS FOR A |
| | SILICONE SYSTEM. FBC 106.1.2* CITY AMENDMENTS |
| | |
| | 7) THE LARGE GLASS BLOCK OPENING ON THE PLANS EXCEEDS |
| | THE MAXIMUM OPENING SIZE OF 6' X 6' ALLOWED BY THE |
| | PRODUCT APPROVAL. DCA RULE 9B-72 |
| | |
| | 8) THE DOOR SCHEDULE ON A-2.0 SPECIFIES AN OXXO DOOR |
| | FOR THE 9' X 8' SLIDING GLASS DOOR. THE FLOOR PLAN AND |
| | ELEVATIONS SHOW A THREE PANEL DOOR. PLEASE CLARIFY. |
| | |
| | 9) WINDOWS #7 AND #5 IN THE SCHEDULE ON A-2.0 WILL BE |
| | REQUIRED TO USE GLASS TYPES B OR D FROM THE PRODUCT |
| | APPROVALS IN ORDER TO MEET THE REQUIRED OPENING |
| | PRESSURES. FBC TABLES R301.2(2) AND R301.2(3). |
| | |
| | 10) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED |
| | TO SECURE THE ROOF TILES. THE HACIENDA TILE SELECTED IN |
| | THE PRODUCT APPROVAL HAS A REQUIRED AERODYNAMIC UPLIFT |
| | MOMENT OF 37 PER TABLE 6 OF THE EVALUATION REPORT. IF |
| | ADHESIVE IS USED, SUBMIT PRODUCT APPROVALS. FBC R 905.3 |
| | AND FBC 106.1.1* CITY AMENDMENTS |
| | |
| | 11) A SEPARATE PERMIT WILL BE REQUIRED FOR THE |
| | DRIVEWAY/APPROACH. |
| | |