| Plan Review Notes For Permit 08040808 |
| Permit Number |
08040808 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-05-02 17:01:07 | RESIDENTIAL (R3)SCREEN ENCLOSURE, BUILDING REVIEW | | | CHECKLIST. | | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | | | 1- ACCORDING TO SEC. 1609.4(3)STRUCTURE IS LOCATED ON | | | EXPOSURE "C", NOT "B".SOUTH EASTQUADRANT OF THE | | | HOUSE IS EXPSOSURE "C".REVISE ALL DESIGN CRITERIA AS | | | REQUIRED TO COMPLY WITH EXPOSURE "C". | | | | | | 2- SITE SPECIFIC DRAWINGS TO SPECIFYALLMEMBERS | | | SIZES, INCLUDINGCORNER COLUMNS,ALL SECONDARY | | | MEMBERS AND BRACING MEMBERS.SEC.106.1.2 CITY | | | AMENDMENTS TO FBC 2004.DRAWINGS SUBMITTED ARE | | | INCOMPLETE. | | | ALSO, THERE IS NOT INFORMATION GIVEN FOR SIDE EAST | | | WALL. | | | | | | 3- SITE SPECIFIC DRAWING GENERAL NOTE #4 STATES THAT | | | DOORSARE OPTIONAL AND CONTRACTOR TO VERIFY LOCATION. | | | THIS IS PART OF THE DESIGN. IF DOORSAREPROVIDED, | | | THEN THEY SHOULD BE SHOWN ON THE SITE SPECIFIC DRAWINGS | | | AND FRAMING MEMBERS SPECIFIED. SEC. 106.1.2 CITY | | | AMENDMENTS TO FBC 2004. | | | | | | 4-ONE DRAWING A-1 IS MISSING THE ENGINEER'S SEAL. | | | ALSO,BOTH DRAWINGS ARE NUMBERED A-1. IT SHOULD BE A-1 | | | AND A-2, NOT BOTH A-1. REVISE AS REQUIRED. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|