| Plan Review Notes For Permit 08040794 |
| Permit Number |
08040794 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-05-09 14:42:15 | ***DENIED*** | | | | | | 1) PLEASE SEE ELECTRICAL COMMENT #1 AND COMPLY. | | | | | | 2) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003 | | | EDITION. | | | | | | 3) WORK TO COMPLY WITH ASME A17.1, SAFETY CODE FOR | | | ELEVATORS AND ESCALATORS. | | | | | | 4) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE | | | SPRINKLER AND FIRE ALARM REMODEL. | | | | | | 5) EMERGENCY WARNING SIGNS ARE REQUIRED IN ELEVATOR | | | LOBBY. | | | | | | 6) PLEASE PROVIDE SECTION OF NFPA 72 THAT DOES NOT | | | REQUIRE SHAFT HEAT DETECTOR TO BE TIED INTO FIRE | | | ALARM. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|