| 2008-05-09 18:02:54 | BUILDING PLAN REVIEW |
| | PERMIT: 08040794 |
| | ADD: 301 N.OLIVE AVE |
| | CONT: THE WEITZ COMPANY |
| | TEL: (561)687-4809 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 5-9-08 |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 2)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS. |
| | |
| | 3)A DESIGN PROFESSIONAL THAT IS REGISTERED TO |
| | PRACTICE UNDER CHAPTER 481 OR 471 OF THE FLORIDA |
| | STATUTES SHALL AFFIX THEIR OFFICIAL SEAL, SIGNATURE AND |
| | DATE TO SAID DRAWINGS AND SPECIFICATIONS PER 106.1 FBC |
| | 2004 |
| | |
| | ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME, ADDRESS, |
| | AND LICENCE NUMBER ON EACH SHEET THAT BEARS THEIR SEAL |
| | PER |
| | 61G15-23.002(2) |
| | |
| | 4)PROVIDE ENGINEERED AND ARCHITECTURAL DRAWINGS |
| | SPECIFIC TO THE PROJECT AND SHOW IN DETAIL HOW THEY |
| | WILL MEET THE REQUIREMENTS OF THE 2004 FBC. SHOW THE |
| | INTERIOR ELEVATION DETAILS OF THE ELEVATORS: THE |
| | INTERIOR ELEVATION DRAWINGS SHALL MEET THE REQUIREMENTS |
| | OF THE SECTION 3007. THE PLANS SUBMITTED ARE MISSING |
| | THE ORIGINAL SEAL AND SIGNATURE OF THE ARCHITECT AND |
| | ENGINEER AND THEY DO NOT SHOW ANY DETAILS OF THE |
| | ELEVATOR INTERIOR.PER FLORIDA STATUTES, 481.229 |
| | EXEMPTIONS FROM ARCHITECTURAL LICENSURE ONLY APPLY TO |
| | 1FAMILY AND 2FAMILY RESIDENCES (R3) NOT MULTI-FAMILY |
| | (R2) OR BUILDINGS OVER $25,000, THEREFORE, DRAWINGS ARE |
| | REQUIRED TO BE DRAWN BY A LICENSED DESIGN PROFESSIONAL. |
| | SEE 471.003 FOR MORE INFORMATION. |
| | |
| | 5)FBC 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |