Plan Review Notes
Plan Review Notes For Permit 08040787
Permit Number 08040787
Review Stop E
Sequence Number 1
Notes
Date Text
2008-05-07 14:27:32 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1AS
 AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PROVIDE A SITE PLAN INDICATING THE LOCATION OF ALL
 THE POLES TO BE INSTALLED AND THE EXISTING POLES FOR
 RECORD RETENTION 106.5 FBC.
  
 2} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE
 PLANS FOR RECORD RETENTION.106.1.3.FBC AS AMENDED.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.
  
 4} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR
 EQUIPMENT BEING WIRED UNDER THIS PERMIT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718