| Date |
Text |
| 2008-06-20 14:05:30 | PLUMBING PLAN REVIEW: |
| | DENIED **2ND TIME: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE |
| | DESIGNER'S RESPONES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | 1. SHEET A.1 FLOOR PLAN EXIST. TOILET #102: THE |
| | REMOVAL OF THE EXISTING LAVATORY AND RELOCATING THE MOP |
| | SINK IN ITS PLACE IS UNACCEPTABLE PER FBC-2004 PLUMBING |
| | SECTION 405.3.2 PUBLIC LAVATORIES. |
| | IN EMPLOYEE AND PUBLIC TOILET ROOMS, THE REQUIRED |
| | LAVATORY SHALL BE LOCATED IN THE SAME ROOM AS THE |
| | REQUIRED WATER CLOSET. |
| | NOTE: THIS DOES NOT SAY FIXTURES CAN BE SUBSTITUTED. |
| | |
| | **RESPONSE NOTED, HOWEVER THE RESUBMITTED PLANS ARE |
| | STILL INDICATING A WATERCLOSET IN EXIST TOILET 102 WITH |
| | THE RELOCATED MOP SINK. CODE CLEARLY INDICATES THE A |
| | LAVATORY SHALL BE LOCATED IN THE BATHROOM WITH A WATER |
| | CLOSET. IF IT IS THE INTENT TO HAVE A UNISEX BATHROOM |
| | AS DISCUSSED IN OUR PHONE CONVERSATION AND MOVE THE MOP |
| | SINK TO ROOM 102 THEN THE WATER CLOSET IN ROOM 102 |
| | SHALL BE DELETED. PER SECTION 405.3.2. ALSO THE |
| | SUBMITTED SANITARY RISER DIAGRAM DOES NOT INDICATE THE |
| | EXISTING SANITARY SYSTEM. PLEASE REMEMBER THE MOP SINK |
| | CAN NOT DRAIN INTO A WET VENTED BATHROOM GROUP, IT MUST |
| | DRAIN DOWNSTREAM OF THE WET VENTED BATHROOM GROUP. |
| | CLEARLY INDICATE HOW THE EXISTING SANITARY IS INSTALLED |
| | AS WELL AS THE PROPOSED TO MEET COMPLIANCE. PER FBC- |
| | PLUMBING SECTION 909.1 WET VENT PERMITTED. |
| | |
| | 2. "OK" COMMENT ADDRESSED. |
| | |
| | 3. "OK" COMMENT ADDRESSED. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |