| Date |
Text |
| 2008-05-14 09:48:11 | |
| | |
| | |
| | |
| | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} INDICATE COMPLIANCE WITH ARTICLE 800.44(B), ABOVE |
| | ROOFS COMMUNICATIONS WIRES AND CABLES SHALL HAVE A |
| | VERTICAL CLEARANCE OF NOT LESS THAN 2.5 M (8 FT) FROM |
| | ALL POINTS OF ROOFS ABOVE WHICH THEY PASS. |
| | * THIS COMMENT WAS MADE TO FOREWARN THE CONTRACTOR THAT |
| | THIS COULD BE AN ISSUE. IT WILL NOW BE RESOLVED AT |
| | INSPECTION. |
| | |
| | 2} 210.52 (A) GENERAL PROVISIONS IN EVERY KITCHEN, |
| | FAMILY ROOM, DINING ROOM, LIVING ROOM, PARLOR, LIBRARY, |
| | DEN, SUNROOM, BEDROOM, RECREATION ROOM, OR SIMILAR ROOM |
| | OR AREA OF DWELLING UNITS, RECEPTACLE OUTLETS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH THE GENERAL PROVISIONS |
| | SPECIFIED IN 210.52(A)(1) THROUGH (A)(3). |
| | |
| | AAMA/NPEA/NSA 2100-02 VOLUNTARY SPECIFICATIONS FOR |
| | SUNROOMS IN THE RESIDENTIAL BUILDING CODE REFERENCES |
| | R301.2.1.1.2 |
| | |
| | R301.2.1.1.2 SUNROOMS. |
| | SUNROOMS SHALL COMPLY WITH AAMA/NPEA/NSA 2100 WITH THE |
| | STRUCTURAL REQUIREMENTS AND TESTING PROVISIONS OF |
| | CHAPTER 5 MODIFIED TO INCORPORATE ASCE 7. NOTE THE TERM |
| | "STRUCTURAL REQUIREMENTS". THIS ARTICLE DOES NOT |
| | SUPERSEDE THE 2005 NEC ARTICLE SITED ABOVE. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |