2009-05-04 15:51:16DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 ****FROM PREVIOUS REVISION REVIEW:
  
 1. SHT P-3 THE SANITARY RISER DIAGRAM AND THE WATER
 RISER DIAGRAM DO NOT REFLECT THE CHANGES INDICATED ON
 SHT P-2 FOR THE BATHROOM CHANGES SUBMITTED THIS
 REVISION. SECTIONS 106.1.1, 601.1 & 701.1.
 ****NEW REVISION FOR SHT P-3 CORRECTED THE SANITARY
 RISER DIAGRAM, BUT NOT THE WATER ISOMETRIC RISER
 DIAGRAM. THERE ARE TWO WATER CLOSETS AND TWO SHOWERS
 SHOWN ON THE REISER DIAGRAM, BUT ONLY ONE WATER CLOSET
 AND ONE SHOWER SHOWN ON THE FLOOR PLAN ON THE WATER
 RISER DIAGRAM. PLEASE CORRELATE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  