| Plan Review Notes For Permit 08040678 |
| Permit Number |
08040678 |
|
| Review Stop |
B |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2009-03-05 15:30:21 | SKYLIGHT REVISION CHECKLIST: | | | | | | 1- SKYLIGHT INFORMATION SUBMITTED FL3130-R3 IS A | | | REVISION, NOT A SUBMITTAL. PRODUCT APPROVAL FOR | | | SKYLIGHT WAS ALREADY APPROVED. IT WAS NOA 07-0810.02. | | | THEREFORE, OWES $80.00 FOR REVISION FEES. | | | | | | 2- PRODUCT APPROVAL FL3130-R3 SUBMITTED DOESN'T MEET | | | THE DESIGN PRESSURES CALCULATED BY THE ARCHITECT. | | | | | | 3- ACCORDING TO HALLMARK CERTIFICATE OF CONFORMANCE AND | | | LICENSE SHEET (CCL) THE PRODUCT APPROVAL IS EXPIRED. | | | NEED TO PROVIDE INFORMATION FOR CURRENT PRODUCT | | | APPROVAL. | | | | | | 4- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT | | | SIGNING AND SEALING) PRODUCT APPROVAL PRIOR TO | | | SUBMITTAL TO THIS OFFICE. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|