Plan Review Notes
Plan Review Notes For Permit 08040678
Permit Number 08040678
Review Stop B
Sequence Number 5
Notes
Date Text
2009-02-18 17:59:12BUILDING REVIEW CHECKLIST FOR ITEMS REQUESTED ON
 PROVISO DATED 08/07/08:
  
  
 ***NOTE: PROVISO WAS ISSUED TO ALLOW CONSTRUCTION TO
 PROCEED AND AVOID CONFLICTS OR DELAYS. AS OF NOW
 PROVISO INFORMATION IS STILL NOT SUBMITTED.
  
  
 1- THIS ITEM WAS ADDRESSED.
  
 2- THIS ITEM WAS NOT ADDRESSED:
 RAS 117 CALCULATIONS FOR WATERPROOFING SYSTEM NEED TO
 BE SIGNED AND SEALED AS REQUIRED BY GENERAL LIMITATION
 #7.
 ***NO INFORMATION SUBMITTED. NEED COMPLETE PRODUCT
 APPROVAL ALONG WITH THE RAS 117 CALCULATIONS. NO
 INFORMATION SUBMITTED.
  
 3- NEED TO PROVIDE ELEVATION CERTIFICATE FOR ENTIRE
 BUILDING AS REQUIRED BY CITY ORDINANCE SEC.
 94-546(B)(1). MIN. FINISH FLOOR ELEVATION TO BE 7.5'
 SINCE BASE FLOOD ELEVATION IS 7.0'.
 ***NOTE: THIS IS TO BE PROVIDED LATER ON TO THE
 BUILDING INSPECTOR PRIOR TO C.O..
  
 4- THIS ITEM WAS NOT ADDRESSED:
 REVISE ENERGY CALCULATIONS TO INCLUDE THE SQUARE
 FOOTAGE FOR NEW STAIRWAY.
 ***NO INFORMATION SUBMITTED.
  
 5- REVISE STAIR CALCULATIONS TO COMPLY WITH RATIO OF
 SEC. R311.5.3.2 OF 2004 FLORIDA RESIDENTIAL CODE.
 ***INFORMATION SUBMITTED ON SHEET A-7 DOESN'T COMPLY
 WITH THE RISER/TREAD RATIO. 6-11/16" RISERS AND 9-1/2"
 TREADS DON'T COMPLY WITH THE 2R+1T RATIO. REVIEW THE
 ABOVE MENTIONED SECTION AND REVISE AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712