| 2009-01-30 13:20:05 | BUILDING REVISION CHECKLIST: |
| | |
| | 1- COMMENTS ON THE REVISION SUBMITTAL FORM ONLY |
| | SPECIFIES REVISION OF STRAPPING AND BOLTING OF BEAMS. |
| | PLANS SUBMITTED SHOWS NOT ONLY STRAPPING AND BOLTING |
| | REVISION BUT FLOOR PLANS REVISIONS AS WELL. WEST |
| | ELEVATION WAS CHANGED ALSO. THEREFORE, NEED TO BRING |
| | PLANS TO HISTORIC TO GET APPROVAL STAMP. |
| | |
| | 2- SHEET S-1: |
| | A) CONNECTOR MTS18 SPECIFIED ON DETAIL 4/S-1 IS NOT A |
| | JOIST HANGER CONNECTOR. THIS CONNECTOR CAN'T BE USED AS |
| | A JOIST HANGER. SEE SIMPSON CATALOG FOR PROPER TYPE OF |
| | HANGER TO BE USED AND REVISE AS REQUIRED. ALSO, REVISE |
| | HANGERS SPECIFIED ON SECOND FLOOR FRAMING PLAN AS |
| | REQUIRED TO MATCH REVISED DETAIL 4/S-1. |
| | |
| | B) CLARIFY WHAT KIND OF CONNECTOR IS JUS210 SPECIFIED |
| | SECOND FLOOR FRAMING PLAN ON BEAM BY MASTER BEDROOM |
| | AREA. |
| | |
| | 3- NEW REVISED FLOOR FRAMING PLANS SHOW NEW AREAS TO |
| | HAVE NEW FRAMING. UPDATE VALUE TO INCLUDE THE |
| | ADDITIONAL WORK AS REQUIRED BY SEC. 108.3 CITY |
| | AMENDMENTS TO FBC 2004. PERMIT FEES WILL BE ADJUSTED |
| | ACCORDINGLY. |
| | |
| | 4- PROVIDE INFORMATION REQUESTED ON PROVISO DATED |
| | 08/07/08. SEE ATTACHED COPY. PROVIDE REQUIRED |
| | INFORMATION TO AVOID CONFLICT OR DELAYS IN THE |
| | CONSTRUCTION PROCESS. |
| | |
| | 5- NUMBER OF REVISED PAGES ARE 10, NOT 4 AS SPECIFIED |
| | ON REVISION SUBMITTAL FORM. THEREFORE OWES $180 FOR |
| | REVISION FEES. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |