| 2008-04-30 09:02:48 | GAS PLAN REVIEW: | | | DENIED: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. SHEET P-3 GAS DISTRIBUTION ISOMETRIC: THE GAS | | | PIPING TO THE TANKLESS WATER HEATER NEEDS TO BE | | | INCREASED TO 1". PER FBC-2004 FUEL GAS TABLES 402.4(2) | | | AND 402.4 (20). PLEASE REFERENCE THE ATTACHED TABLES TO | | | THESE COMMENTS INDICATING THIS FOR THE RESUBMITTAL. | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION | | | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | NOTE: THERE IS ONLY ONE CORRECTED DRAWING | | | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS | | | EXAMINER FOR REFERENCE FOR THE | | | RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|