| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004 |
| | FBC CHAPTER 1 AS AMENDED AND FOUND NONCOMPLIANT WITH |
| | THE FOLLOWING: |
| | |
| | 1} REGARDING THE MAIN HOUSE DISCONNECT , SHEET E-3, A |
| | GROUNDING ELECTRODE CONDUCTOR IS REQUIRED AT THE |
| | SEPARATE STRUCTURE PER 250.32, SIZED PER 250.66. |
| | |
| | 2} CIRCUIT B-3 LISTED AS THE LAUNDRY CIRCUIT IS IN |
| | VIOLATION OF 210.11(C)(2) "THIS CIRCUIT SHALL HAVE NO |
| | OTHER OUTLETS." THE LIGHTS CANNOT BE ON THE CIRCUIT. |
| | |
| | 3} THE DRYER LISTED ON CIRCUIT 4-6 PANEL "B" APPEARS TO |
| | BE A STACK UNIT ON SHEET E-1, CLARIFY AND CORRECT |
| | SCHEDULE "B" ACCORDINGLY. |
| | |
| | 4} LOCATE BOTH AHU'S ON THE PLAN.106.1.1 FBC. |
| | |
| | 5} BATH CIRCUIT B-5 DOES NOT COMPLY WITH 210.11(C)(3) |
| | "SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS." THE |
| | RECEPTACLE IN THE "POWDER" AND BATH" ROOM, SHEET E-1 |
| | COULD BE ON THAT CIRCUIT, BUT NOT THE LIGHTS.OR THE |
| | LIGHTS AND RECEPTACLE IN EITHER ONE COULD BE ON THAT |
| | CIRCUIT. SEE EXCEPTION: WHERE THE 20-AMPERE CIRCUIT |
| | SUPPLIES A SINGLE BATHROOM, OUTLETS FOR OTHER EQUIPMENT |
| | WITHIN THE SAME BATHROOM SHALL BE PERMITTED TO BE |
| | SUPPLIED IN ACCORDANCE WITH 210.23(A)(1) AND (A)(2). |
| | |
| | 6} CIRCUIT B7 INDICATES IT SERVES THE HALL AS WELL AS |
| | THE BEDROOM. SHEET E-1 INDICATES CIRCUIT B12 IN THE |
| | HALL, CORRELATE THE CIRCUITS. |
| | |
| | 210.52(E) OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING AND |
| | EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE |
| | LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT |
| | GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE |
| | GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE |
| | DWELLING. |
| | |
| | NOTE: CONFIRM THE AHU LOADS ARE 4800 WATTS TOTAL HEAT |
| | FOR 2855 SQ FT RESIDENCE. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |