| 2008-05-05 16:23:15 | RESIDENTIAL (R3) ADDITION AND ALTERATION, BUILDING |
| | REVIEW CHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDA STATUTE. |
| | |
| | 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD |
| | (561)233-5120)TO CHECK IF IMPACT FEES ARE DUE. BRING |
| | BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE |
| | DUE. |
| | |
| | 3- AREA CALCULATIONS ON SHEET SP-1 NEED TO SPECIFY |
| | ADDITION AREAS INCLUDING THE NEW STAIRWAY AND ADDITION |
| | FOR NEW GUEST ROOM TO PROPERLY ASSESS THE RADON FEES. |
| | |
| | 4- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | A) ROOF TILE. |
| | B) POLYFOAM IF USED FOR ROOF TILE. |
| | C) * FLAT ROOF APPROVED ASSEMBLY ON PAGE 4 OF NOA |
| | 07-0212.03 IS FOR AN INSULATED ASSEMBLY. PLANS DON'T |
| | SHOW AN INSULATED ASSEMBLY. CLARIFY/REVISE AS |
| | REQUIRED. |
| | ** PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT |
| | PERIMETER AND CORNER AREASAS REQUIRED BY GENERAL |
| | LIMITATION #7. |
| | ***NOTE: THIS SYSTEM WILL REQUIRE AT LEAST 4 ROWS IN |
| | THE FIELD AREA OF THE ROLL. SEE ATTACHED CALCULATIONS. |
| | 3" SPACING IS NOT ALLOWED. |
| | D) FRENCH DOORS THAT RESIST THE DESIGN PRESSURES |
| | CALCULATED ON SHEET S-3 FOR D2 DOORS. |
| | E) SKYLIGHT ABOVE STAIRWAY. |
| | |
| | 5- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND |
| | APPROVED IN WRITING (NOT SIGNING AND SEALING).PRODUCT |
| | APPROVALS SUBMITTED HAVE THE REVIEW STAMP, BUT THEY |
| | WERE NOT SIGNED. ONLY THE DATE WAS PROVIDED. |
| | |
| | 6- ENERGY CALCULATIONS: |
| | A) COMPLETE ALL THE INFORMATION ON TOP OF FORM. |
| | |
| | B ) SPECIFY HOW IS THE R6.0 INSULATION INSTALLED ON |
| | THE CONCRETE SLAB. SEE ITEM #8(A). |
| | C) NEED TO ADD THE AREA FOR THE ADDITION BY NEW |
| | GUEST ROOM.ALSO,WINDOWS AND DOORSON THE GUEST |
| | ROOM NEED TO BE INCLUDED ON THE SECOND PAGE. |
| | D) COMPLETE THE CODE COMPLIANCE CHECKLIST. |
| | |
| | ***NOTE: SHORT FORM 600C-04R IS THE MOST ADEQUATE FORM |
| | TO BE USED FOR THIS PROJECT INSTEAD OF THE 600A-04R |
| | FORM SUBMITTED. |
| | |
| | 7- ELEVATION CERTIFICATE NEED TO HAVE SURVEYORS |
| | ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 472 |
| | FLORIDA STATUTE.THISCERTIFICATE WILL BE REQUIRED AT |
| | THE END OF THE CONSTRUCTION TO GET THE C.O. |
| | |
| | 8- DOOR #11 SPECIFIED FOR NEW GUEST BATHROOM IN THE |
| | DOOR SCHEDULEDOESN'T MATCHDOOR SHOWN ON FIRST FLOOR |
| | PLAN. REVISE AS REQUIRED. |
| | |
| | 9- PROVIDE SPECIFICATIONS FOR ICYNENE INSULATION TO |
| | VERIFY COMPLIANCE WITHENERGY CALCULATIONS AND PLAN |
| | SPECIFICATIONS. |
| | |
| | 10- SHEET A-7:A) REVISE STAIR CALCULATIONS TO COMPLY |
| | WITH SEC. R311.5.3.2 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | NEED RISER AND TREAD RATIO BETWEEN 24 AND 25. |
| | B) REVISE RAILING DETAILTO COORDINATE WITH RISER |
| | AND TREAD DIMENSIONS SHOWN ON SECTION A-STAIR DETAIL |
| | AND FLOOR PLANS. ALSO, COORDINATE WITH ITEM #7(A) |
| | ABOVE. |
| | |
| | 11- SHEET S-1: A) SPECIFY CONNECTORS AT THE ENDS OF NEW |
| | BEAMS WHERE OLD STAIRS WERE DEMOLISHED. |
| | B) DETAIL 3/S-1: SPECIFY SIZE OF REBAR CONNECTING |
| | EXISTING FOOTING TO NEW FOOTING. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |