Plan Review Notes
Plan Review Notes For Permit 08040678
Permit Number 08040678
Review Stop B
Sequence Number 1
Notes
Date Text
2008-05-05 16:23:15RESIDENTIAL (R3) ADDITION AND ALTERATION, BUILDING
 REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD
 (561)233-5120)TO CHECK IF IMPACT FEES ARE DUE. BRING
 BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE
 DUE.
  
 3- AREA CALCULATIONS ON SHEET SP-1 NEED TO SPECIFY
 ADDITION AREAS INCLUDING THE NEW STAIRWAY AND ADDITION
 FOR NEW GUEST ROOM TO PROPERLY ASSESS THE RADON FEES.
  
 4- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) ROOF TILE.
 B) POLYFOAM IF USED FOR ROOF TILE.
 C) * FLAT ROOF APPROVED ASSEMBLY ON PAGE 4 OF NOA
 07-0212.03 IS FOR AN INSULATED ASSEMBLY. PLANS DON'T
 SHOW AN INSULATED ASSEMBLY. CLARIFY/REVISE AS
 REQUIRED.
 ** PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREASAS REQUIRED BY GENERAL
 LIMITATION #7.
 ***NOTE: THIS SYSTEM WILL REQUIRE AT LEAST 4 ROWS IN
 THE FIELD AREA OF THE ROLL. SEE ATTACHED CALCULATIONS.
 3" SPACING IS NOT ALLOWED.
 D) FRENCH DOORS THAT RESIST THE DESIGN PRESSURES
 CALCULATED ON SHEET S-3 FOR D2 DOORS.
 E) SKYLIGHT ABOVE STAIRWAY.
  
 5- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND
 APPROVED IN WRITING (NOT SIGNING AND SEALING).PRODUCT
 APPROVALS SUBMITTED HAVE THE REVIEW STAMP, BUT THEY
 WERE NOT SIGNED. ONLY THE DATE WAS PROVIDED.
  
 6- ENERGY CALCULATIONS:
 A) COMPLETE ALL THE INFORMATION ON TOP OF FORM.
  
 B ) SPECIFY HOW IS THE R6.0 INSULATION INSTALLED ON
 THE CONCRETE SLAB. SEE ITEM #8(A).
 C) NEED TO ADD THE AREA FOR THE ADDITION BY NEW
 GUEST ROOM.ALSO,WINDOWS AND DOORSON THE GUEST
 ROOM NEED TO BE INCLUDED ON THE SECOND PAGE.
 D) COMPLETE THE CODE COMPLIANCE CHECKLIST.
  
 ***NOTE: SHORT FORM 600C-04R IS THE MOST ADEQUATE FORM
 TO BE USED FOR THIS PROJECT INSTEAD OF THE 600A-04R
 FORM SUBMITTED.
  
 7- ELEVATION CERTIFICATE NEED TO HAVE SURVEYORS
 ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 472
 FLORIDA STATUTE.THISCERTIFICATE WILL BE REQUIRED AT
 THE END OF THE CONSTRUCTION TO GET THE C.O.
  
 8- DOOR #11 SPECIFIED FOR NEW GUEST BATHROOM IN THE
 DOOR SCHEDULEDOESN'T MATCHDOOR SHOWN ON FIRST FLOOR
 PLAN. REVISE AS REQUIRED.
  
 9- PROVIDE SPECIFICATIONS FOR ICYNENE INSULATION TO
 VERIFY COMPLIANCE WITHENERGY CALCULATIONS AND PLAN
 SPECIFICATIONS.
  
 10- SHEET A-7:A) REVISE STAIR CALCULATIONS TO COMPLY
 WITH SEC. R311.5.3.2 OF 2004 FLORIDA RESIDENTIAL CODE.
 NEED RISER AND TREAD RATIO BETWEEN 24 AND 25.
 B) REVISE RAILING DETAILTO COORDINATE WITH RISER
 AND TREAD DIMENSIONS SHOWN ON SECTION A-STAIR DETAIL
 AND FLOOR PLANS. ALSO, COORDINATE WITH ITEM #7(A)
 ABOVE.
  
 11- SHEET S-1: A) SPECIFY CONNECTORS AT THE ENDS OF NEW
 BEAMS WHERE OLD STAIRS WERE DEMOLISHED.
 B) DETAIL 3/S-1: SPECIFY SIZE OF REBAR CONNECTING
 EXISTING FOOTING TO NEW FOOTING.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712