| Plan Review Notes For Permit 08040677 |
| Permit Number |
08040677 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-05-05 10:58:25 | ***DENIED*** | | | | | | 1) PLEASE SEE ELECTRICAL COMMENT #3 REGARDING | | | REQUIREMENTS FOR PLANS. ADDITIONALLY, ADDRESS OF | | | PROJECT SHALL BE DISPLAYED IN TITLE BLOCK OF ALL SHEETS | | | AND ASSOCIATED DOCUMENTS. | | | | | | 2) PROVIDE THE PRESCRIPTIVE STRENGTH REQUIREMENTS FOR | | | HANDRAILS. | | | | | | 3) A FIRE DEPARTMENT KNOX SWITCH IS SHOWN AT ENTRY | | | GATE. PLEASE INDICATE WHERE MINIMUM WIDTH AND HEIGHT | | | REQUIREMENTS FOR FIRE APPARATUS HAS BEEN PROVIDED. | | | | | | 4) PLEASE PROVIDE APPROPRIATE CUT SHEETS FOR EQUIPMENT, | | | IE CARD READERS, MAG LOCKS ETC. IS A FAILSAFE MECHANISM | | | PROVIDED SHOULD LOSS OF POWER OCCUR? | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|