| Plan Review Notes For Permit 08040672 |
| Permit Number |
08040672 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2008-06-18 14:00:37 | SPACE PAK HIGH VELOCITY SYSTEM | | | | | | *** PROVISO *** | | | 1) IF PLASTIC REGISTERS, GRILLES OR DIFFUSERS ARE USED | | | THEN PROVIDE UL TESTING REPORT. | | | PER 2004 FBC/R M1601.16 DUCT REGISTERS, GRILLES AND | | | DIFFUSERS SHALL BE INSTALLED IN ACCORDANCE WITH THE | | | MANUFACTURER'S INSTALLATION INSTRUCTIONS, AND SHALL | | | HAVE A FLAME SPREAD RATING NOT OVER 25 WITHOUT EVIDENCE | | | OF CONTINUED PROGRESSIVE COMBUSTION AND A | | | SMOKE-DEVELOPED RATING NOT OVER 50 WHEN TESTED IN | | | ACCORDANCE WITH ASTM E 84. BALANCING DAMPERS OR OTHER | | | MEANS OF SUPPLY AIR ADJUSTMENT SHALL BE PROVIDED IN THE | | | BRANCH DUCTS OR AT EACH INDIVIDUAL DUCT REGISTER, | | | GRILLE OR DIFFUSER. | | | | | | 2) HAVE DETAILED MANUFACTURER'S SPECIFICATION'S AND | | | INSTALLATION INSTRUCTIONS FOR A/C SYSTEM AND | | | PRE-ENGINEERED DUCT SYSTEM ON JOB SITE FOR CITY | | | INSPECTORS. PER 2004 FBC/R M1401.1. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|