2008-06-18 14:00:37SPACE PAK HIGH VELOCITY SYSTEM
  
 *** PROVISO ***
 1) IF PLASTIC REGISTERS, GRILLES OR DIFFUSERS ARE USED
 THEN PROVIDE UL TESTING REPORT.
 PER 2004 FBC/R M1601.16 DUCT REGISTERS, GRILLES AND
 DIFFUSERS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS, AND SHALL
 HAVE A FLAME SPREAD RATING NOT OVER 25 WITHOUT EVIDENCE
 OF CONTINUED PROGRESSIVE COMBUSTION AND A
 SMOKE-DEVELOPED RATING NOT OVER 50 WHEN TESTED IN
 ACCORDANCE WITH ASTM E 84. BALANCING DAMPERS OR OTHER
 MEANS OF SUPPLY AIR ADJUSTMENT SHALL BE PROVIDED IN THE
 BRANCH DUCTS OR AT EACH INDIVIDUAL DUCT REGISTER,
 GRILLE OR DIFFUSER.
  
 2) HAVE DETAILED MANUFACTURER'S SPECIFICATION'S AND
 INSTALLATION INSTRUCTIONS FOR A/C SYSTEM AND
 PRE-ENGINEERED DUCT SYSTEM ON JOB SITE FOR CITY
 INSPECTORS. PER 2004 FBC/R M1401.1.
  