2008-06-17 10:35:14PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE PLAN SUBMITTED SHOWS THE SUPPLY DUCTS AS 4" THIS
 IS A PER ENGINEERED SYSTEM AND THE MANUFACTURE STATES
 THE SUPPLY TUBING (DUCTS) NEED TO BE 2' (SEE ATTACHED
 MANUFACTURE SPEC. SHEET) PLEASE CORRECT, PER 2004 FBC/R
 M1401.1.
  
 2) THE PLAN SHOWS A 28X20 RETURN AIR GRILL IN A CLOSET
 (SEE YELLOW HIGH LIGHT ON PLAN) PLEASE EXPLAIN OR
 CORRECT, PER 2004 FBC/R M1602.2 (3).
  
 3) PLAN SHOWS NO RETURN AIR GRILL IN THE HALL FOR
 COMMON RETURN, ONLY A MIXING BOX ABOVE, PLEASE EXPLAIN
 OR CORRECT, PER 2004 FBC/R M1602.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]