| Plan Review Notes For Permit 08040672 |
| Permit Number |
08040672 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-06-17 10:35:14 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) THE PLAN SUBMITTED SHOWS THE SUPPLY DUCTS AS 4" THIS | | | IS A PER ENGINEERED SYSTEM AND THE MANUFACTURE STATES | | | THE SUPPLY TUBING (DUCTS) NEED TO BE 2' (SEE ATTACHED | | | MANUFACTURE SPEC. SHEET) PLEASE CORRECT, PER 2004 FBC/R | | | M1401.1. | | | | | | 2) THE PLAN SHOWS A 28X20 RETURN AIR GRILL IN A CLOSET | | | (SEE YELLOW HIGH LIGHT ON PLAN) PLEASE EXPLAIN OR | | | CORRECT, PER 2004 FBC/R M1602.2 (3). | | | | | | 3) PLAN SHOWS NO RETURN AIR GRILL IN THE HALL FOR | | | COMMON RETURN, ONLY A MIXING BOX ABOVE, PLEASE EXPLAIN | | | OR CORRECT, PER 2004 FBC/R M1602.4. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|