2008-04-25 09:26:14PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) PLEASE SUBMIT MANUAL D CALCULATIONS FOR RESIDENTIAL
 DUCT DESIGN, PER 2004 FBC/R M1601.1.
  
 2) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR THE
 AIR DIFFUSERS SHOWING THEIR FLAME SPREAD RATING AND
 SMOKE-DEVELOPED RATING. PER 2004 FBC/R M1601.16
 REGISTERS, GRILLES AND DIFFUSERS.
 DUCT REGISTERS, GRILLES AND DIFFUSERS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS, AND SHALL HAVE A FLAME
 SPREAD RATING NOT OVER 25 WITHOUT EVIDENCE OF CONTINUED
 PROGRESSIVE COMBUSTION AND A SMOKE-DEVELOPED RATING NOT
 OVER 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84.
 BALANCING DAMPERS OR OTHER MEANS OF SUPPLY AIR
 ADJUSTMENT SHALL BE PROVIDED IN THE BRANCH DUCTS OR AT
 EACH INDIVIDUAL DUCT REGISTER, GRILLE OR DIFFUSER.
  
 3) PLEASE SHOW THE CFM'S AT ALL SUPPLY AIR DIFFUSERS,
 PER WPB AMEND. 106.3.5.4 (10).
  
 4) PLEASE SHOW THE SEER OF THE A/C SYSTEM IN THE
 EQUIPMENT SCHEDULE ON THE PLAN.
  
 5) A/C SYSTEM MODEL NUMBERS LISTED ON THE A/C EQUIPMENT
 SCHEDULE COULD NOT BE FOUND ON THE ARI DIRECTORY
 WEB-SITE, PLEASE CORRECT OR SUBMIT AN ARI CERTIFICATE,
 SEE 2004 FBC 13-407.1.ABC.3.1.1 OR 13-607.1.ABC.3.1.1.
  
 MECHANICAL PLAN REVIEW BY;