| 2008-05-20 15:20:11 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | |
| | 1.AS DISCUSSED, PROVIDE MORE INFORMATION REGARDING |
| | WHO WILL ACTUALLY INSTALL THE SHUTTERS.THE CONTRACT |
| | PROVIDED IS AN AGREEMENT TO ACT AS A LEASING AGENT; IT |
| | HAS NO INFORMATION REGARDING HURRICANE SHUTTER |
| | INSTALLATION.I ALSO STATES THAT HE MANAGES HUNDREDS |
| | OF PROPERTIES.IF MR. FORD MANAGES HUNDREDS OF |
| | PROPERTIES, HOW WILL HE GET THE SHUTTERS INSTALLED ON |
| | THIS BUILDING? |
| | |
| | 2.SEE PREIVOUS LIST.PLEASE ADDRESS THE ISSUE OF |
| | WHEN THE SHUTTERS WILL BE REMOVED FROM THE BUILDNG OR, |
| | AS DISCUSSED, INDICATE THAT ONE WINDOW IN EACH BEDROOM |
| | WILL BE IMPACT RATED. |
| | |
| | 3.THE PRESTORM PREPARATION PLAN MAY BE SUBMITTED VIA |
| | EMAIL FOR PRELIMINARY REVIEW.ONCE FINALIZED AND IF |
| | APPROVED BY BUILDING OFFICIAL, AN ORIGINAL SIGNED BY |
| | THE OWNER WILL BE REQUIRED. |
| | |
| | 4.SEE THE INSTALLATION SCHEDULE.THE ITW TAPCON, |
| | 444.2PSF, C1 CONNECTION, HOLLOW BLOCK (PAGE 5) REQUIRES |
| | 7" ANCHOR SPACING.10" AND 5" SPECIFIED ON THE |
| | INSTALLATION SCHEDULE; PLEASE REVISE. |
| | |
| | THIS WAS ON S.HILL'S DESK PENDING INFORMATION FROM THE |
| | CONTRACTOR.THE PLANS HAVE BEEN ROUTED TO THE FRONT |
| | DESK PENDING APPROVAL OF THE PRESTORM PREPARATION PLAN. |
| | A RESUBMITTAL IS REQUIRED; INSTALLATION SCHEDULE MUST |
| | BE REVISED (NOT CODE COMPLIANT AS SUBMITTED). |