| 2008-08-18 10:13:10 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 1.ADDRESSED. |
| | |
| | 2.THE INSTALLATION SCHEDULE SHUTTER CONNECTION |
| | MOUNTING TYPE IS TO CORRELATE WITH THE ANCHOR SCHEDULE. |
| | YOU'VE CIRCED ANCHORING FOR BOTTOM 8.SPECIFY BOTH TOP |
| | AND BOTTOM ANCHOR CONNECTION TYPE ON THE INSTALLATION |
| | SCHEDULE FORM. |
| | |
| | 2ND REVIEW, PLEASE REVISE SHUTTER CONNECTION MOUNTING |
| | TYPE TO CORRELATE WITH THE ANCHORS SCHEDULES.FOR THE |
| | ACCORDIONS, THIS SHOULD BE C1 THROUGH C5.FOR THE |
| | PANELS, WALL MOUNT 1 THROUGH 13.PLEASE NOTE THAT |
| | OPENING 1 SPECIFIES TAPCONS, BUT CIRCLED ANCHOR SPACING |
| | FOR SOLID SET FOR BOTTOM 8 (TAPCONS NOT PERMITTED FOR |
| | THAT SPAN, SHUTTER CONNECTION MOUNTING TYPE). |
| | |
| | 3RD REVIEW, INSTALLATION SCHEDULE STATES WALL.THERE |
| | ARE DIFFERENT TYPES OF WALL MOUNT, EACH WITH DIFFERENT |
| | ANCHOR SPACING REQUIREMENTS.PLEASE REVISE AS |
| | REQUESTED. |
| | |
| | 3.ADDRESSED. |
| | |
| | 4.THE SPAN IS ONE DIMENSION.PLEASE REVISE.THIS IS |
| | THE DISTANCE ANCHOR TO ANCHOR OR BLADE LENGTH, |
| | DEPENDING ON TYPE OF SHUTTER. |
| | |
| | 2ND REVIEW, THIS WAS NOT ADDRESSED BUT AS VERTICAL WAS |
| | SPECIFIED, I USED THAT DIMENSION FOR THE REVIEW. |
| | |
| | 3RD REVIEW, NOT ADDRESSED.PLEASE SPECIFY SPAN. |
| | |