2008-04-29 11:16:512004 FBC WITH 2007 REVISIONS
 SCREEN ENCLOSURE
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED.
  
 2) THE BEAM SIZES FOR THE COLUMNS HEIGHTS ARE TOO
 SMALL. THE CARRIER BEAMS ARE TOO SMALL FOR THE SPANS.
 PLEASE CORRECT. PLEASE MARK THE APPROPRIATE ITEMS IN
 THE ENGINEER'S BEAM AND COLUMN SCHEDULES.
  
 3) THE SITE ENGINEERING IS FOR EXPOSURE CATEGORY "B"
 AND THE GENERIC ENGINEERING WITH THE SCHEDULES IS FOR
 EXPOSURE "C". PLEASE COORDINATE THE ENGINEERING.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW