| Plan Review Notes For Permit 08040649 |
| Permit Number |
08040649 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-04-25 08:22:39 | 2004 FBC W/2007 REVISIONS | | | INSTALL ACCORDION SHUTTERS | | | | | | DENIED BY BUILDING | | | | | | 1) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C. THE | | | DESIGN PRESSURE CALCULATIONS THAT WERE SUBMITTED ARE | | | FOR EXPOSURE B, PLEASE CORRECT. SEE FBC R301.2.1.4 | | | WHICH REVISED THE DEFINITION OF EXPOSURE C TO INCLUDE | | | BUILDINGS ADJACENT TO OPEN AREAS OF EXPOSURE TYPE C | | | TERRAIN IN ANY QUADRANT FOR A DISTANCE OF MORE THAN 600 | | | FEET. PLEASE REVISE CALCULATIONS. | | | | | | 2) ON SHEET 5 OF THE DRAWINGS WALL MOUNT SECTION F IS | | | CIRCLED. THE CONNECTION TYPE FOR THIS MOUNT IS C2 AT | | | THE TOP AND BOTTOM. ON THE ANCHOR SCHEDULE ON SHEET 7, | | | THE ANCHOR SPACING THAT IS CIRCLED IS FOR C3 CONNECTION | | | TYPE. PLEASE CORRECT. | | | | | | 3) THE HEIGHT OF ONE OPENING IS SPECIFIED AS 77"WHICH | | | IS A SPAN MORE THAN 6'-0". ON SHEET 7 THE FASTENER | | | SPACING THAT WAS CIRCLED IS IN THE COLUMN FOR SPANS NOT | | | EXCEEDING 6'-0". PLEASE CORRECT. | | | | | | 4) UNLESS THE ANCHORS ARE BEING INSTALLED INTO A | | | MINIMUM OF 3,000 PSI CONCRETE, THE TABLE FOR HOLLOW | | | CONCRET BLOCK SHOULD BE USED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|