| Date |
Text |
| 2008-06-03 11:30:26 | PLUMBING PLAN REVIEW: |
| | DENIED **2ND TIME: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE |
| | DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | 1. SHEET P.1 SANITARY RISER DIAGRAM AND PLUMBING PLAN: |
| | FIXTURE SK-1 MUST DRAIN DOWNSTREAM OF THE WET VENTED |
| | BATHROOM GROUP IN ROOM #103. PER FBC-2004 PLUMBING |
| | SECTION 909.1 WET VENT PERMITTED. |
| | |
| | **RESPONSE NOTED, HOWEVER THE RESUBMITTED SHEET P.1 |
| | STILL INDICATES FIXTURE SK-1 DRAINING INTO THE WET |
| | VENTED BATHROOM GROUP (WATER CLOSET AND LAVATORY) OF |
| | RESTROOM #2. FIXTURE SK-1 NEEDS TO DRAIN DOWNSTREAM OF |
| | THE WET VENTED BATHROOM. PER FBC-2004 PLUMBING SECTION |
| | 909.1 WET VENT PERMITTED. |
| | |
| | 2. SHEET A.1 AND P.1 PLEASE CLARIFY IF SINK SK-1 IS A |
| | WORK RELATED SINK OR IS THIS SINK FOR A BREAK AREA? IF |
| | THIS SINK IS FOR A BREAK AREA PLEASE PROVIDE THE |
| | FOLLOWING PER FBC FLORIDA ACCESSIBILITY CODE CHAPTER 11 |
| | SECTIONS 11-4.24.1 THRU 11-4.24.6. WITH AN ELEVATION |
| | DETAIL. PER (W.P.B. AS AMENDED) SECTION 106.1.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS AND SECTION |
| | 106.1.2 ADDITIONAL DATA. |
| | |
| | **RESPONSE NOTED, HOWEVER THE RESUBMITTED DETAIL ON |
| | SHEET A.1 DETAIL 3/A.1 DOES NOT CLEARLY INDICATE THE |
| | FOLLOWING. THE CLEAR FLOOR SPACE NEEDS TO BE INDICATED |
| | ON THE FLOOR PLAN ON SHEET A.1. |
| | |
| | 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR |
| | SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE |
| | SINK. |
| | 11-4.24.6 EXPOSED PIPES AND SURFACES. INSULATE TO |
| | PROTECT AGAINST CONTACT. |
| | 11-4.24.7 FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR |
| | ELECTRONICALLY CONTROLLED ARE ACCEPTABLE DESIGNS. |
| | |
| | 3. "OK" COMMENT ADDRESSED. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |