Plan Review Notes
Plan Review Notes For Permit 08040631
Permit Number 08040631
Review Stop P
Sequence Number 2
Notes
Date Text
2008-06-03 11:30:26PLUMBING PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. SHEET P.1 SANITARY RISER DIAGRAM AND PLUMBING PLAN:
 FIXTURE SK-1 MUST DRAIN DOWNSTREAM OF THE WET VENTED
 BATHROOM GROUP IN ROOM #103. PER FBC-2004 PLUMBING
 SECTION 909.1 WET VENT PERMITTED.
  
 **RESPONSE NOTED, HOWEVER THE RESUBMITTED SHEET P.1
 STILL INDICATES FIXTURE SK-1 DRAINING INTO THE WET
 VENTED BATHROOM GROUP (WATER CLOSET AND LAVATORY) OF
 RESTROOM #2. FIXTURE SK-1 NEEDS TO DRAIN DOWNSTREAM OF
 THE WET VENTED BATHROOM. PER FBC-2004 PLUMBING SECTION
 909.1 WET VENT PERMITTED.
  
 2. SHEET A.1 AND P.1 PLEASE CLARIFY IF SINK SK-1 IS A
 WORK RELATED SINK OR IS THIS SINK FOR A BREAK AREA? IF
 THIS SINK IS FOR A BREAK AREA PLEASE PROVIDE THE
 FOLLOWING PER FBC FLORIDA ACCESSIBILITY CODE CHAPTER 11
 SECTIONS 11-4.24.1 THRU 11-4.24.6. WITH AN ELEVATION
 DETAIL. PER (W.P.B. AS AMENDED) SECTION 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS AND SECTION
 106.1.2 ADDITIONAL DATA.
  
 **RESPONSE NOTED, HOWEVER THE RESUBMITTED DETAIL ON
 SHEET A.1 DETAIL 3/A.1 DOES NOT CLEARLY INDICATE THE
 FOLLOWING. THE CLEAR FLOOR SPACE NEEDS TO BE INDICATED
 ON THE FLOOR PLAN ON SHEET A.1.
  
 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR
 SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK.
 11-4.24.6 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.24.7 FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR
 ELECTRONICALLY CONTROLLED ARE ACCEPTABLE DESIGNS.
  
 3. "OK" COMMENT ADDRESSED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved