2008-04-24 18:31:132004 FBC W/2007 REVISIONS
 REPLACE GARAGE DOOR
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C. THE
 REQUIRED COMPONENT AND CLADDING WINDLOAD PRESSURE IS
 MORE THAN THE DESIGN PRESSURE OF THE PRODUCT APPROVAL.
 SUBMIT A PRODUCT APPROVAL FOR A DOOR WITH A GREATER
 DESIGN PRESSURE. SEE FBC TABLE R301.2(4) AND R301.2(3)
 HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENTS.
  