2008-06-20 16:57:59** REDLINED NOTES **
  
  
 1) NOTE:BATTERY BACK UP LIGHTING IS REQUIRED FOR
 MINIMUM 1FT CANDLE FOR EGRESS IN HALLWAYS AND
 MULTI-GANG BATHROOMS IF BUILDING IS OCCUPIED UNDER
 EMERGENCY POWER.
 NFPA-101 7.9 PERMITS THE GENERATOR FOR BACK UP OF
 EGRESS LIGHTING FOR THE OCCUPANTS TO LEAVE THE PREMISES
 AND BUILDING IS TO REMAIN UNOCCUPIED UNTIL NORMAL POWER
 IS BACK TO NORMAL.
 IF BUILDING IS NOT GOING TO BE OCCUPIED UNDER THE BACK
 UP OF THE GENERATOR THE HALLWAYS MAY REMAIN ON
 GENERATOR HOWEVER BATHROOMS WILL REQUIRED A MINIMUM OF
 ONE TYPE OF BATTERY BACK UP FIXTURE.
  
 IF THERE ARE NAY QUESTIONS PLEASE CONTACT THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]