| Plan Review Notes For Permit 08040612 |
| Permit Number |
08040612 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-06-20 16:57:59 | ** REDLINED NOTES ** | | | | | | | | | 1) NOTE:BATTERY BACK UP LIGHTING IS REQUIRED FOR | | | MINIMUM 1FT CANDLE FOR EGRESS IN HALLWAYS AND | | | MULTI-GANG BATHROOMS IF BUILDING IS OCCUPIED UNDER | | | EMERGENCY POWER. | | | NFPA-101 7.9 PERMITS THE GENERATOR FOR BACK UP OF | | | EGRESS LIGHTING FOR THE OCCUPANTS TO LEAVE THE PREMISES | | | AND BUILDING IS TO REMAIN UNOCCUPIED UNTIL NORMAL POWER | | | IS BACK TO NORMAL. | | | IF BUILDING IS NOT GOING TO BE OCCUPIED UNDER THE BACK | | | UP OF THE GENERATOR THE HALLWAYS MAY REMAIN ON | | | GENERATOR HOWEVER BATHROOMS WILL REQUIRED A MINIMUM OF | | | ONE TYPE OF BATTERY BACK UP FIXTURE. | | | | | | IF THERE ARE NAY QUESTIONS PLEASE CONTACT THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|