| Date |
Text |
| 2008-04-29 15:57:35 | ** DENIEDREVIEW ** |
| | |
| | 1) NOTE: |
| | |
| | 2) NOTE: PLEASE INDICATE THE MAXIMUM TIMES ON OCCUPANCY |
| | SENSOR LISTED ON SYMBOL LEGEND. |
| | FBC 13-415.1.ABC.1.1, .1.2 |
| | |
| | 3) NOTE: PLEASE SHOW/INDICATE EMERGENCY LIGHTING IN |
| | EACH OF THE MULTI-GANG RESTROOMS. ONE FIXTURE MINIMUM |
| | IS REQUIRED IN EACH FOR 1FT CANDLE MINIMUM LEVEL UNDER |
| | EMERGENCY CONDITIONS. |
| | LS 101 7.9 |
| | |
| | 4) NOTE: PLEASE VERIFY THE EXISTING PANEL 16EL1. THIS |
| | IS SHOWN AS A 100AMP YET THE INFORMATION STATE ON PANEL |
| | MENTIONS A NEW 200AMP MAIN CIRCUIT BREAKER. |
| | PLEASE ALSO VERIFY RATING OF PANEL WHICH STATES |
| | 240/480, AND OPERATING VOLTAGE OF 277/480V. |
| | 110.3, 90.7 |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION AND |
| | COORDINATION. |
| | |
| | 5) NOTE: PLEASE VERIFY ANY HORN/STROBES IN RESTROOMS |
| | PER FBC 11-4.28.1, .2 AND PLEASE VERIFY LEVELS PER |
| | .3(4) FOR ADA. |
| | |
| | 6) NOTE: PLEASE BE SURE THE 2003 NFPA-101, 2002 NFPA-72 |
| | IS LISTED ON ELECTRICAL PLANS. |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |