2008-04-24 08:34:19GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. PER FBC FUEL GAS SECTION 401.1 SCOPE.
 *THE SUBMITTED ISOMETRIC IS NOT INDICATING THE
 CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE.
 REFERENCE THE RED CIRCLED YELLOW HIGH LIGHTED CUT
 SECTIONS THAT ARE NOT COMPLIANT.PLEASE CORRECT AND
 RESUBMIT.
  
 2. CLEARLY INDICATE THE TYPE OF GAS, (LP OR NATURAL)
 ON THE DRAWINGS. PER FBC FUEL GAS SECTION 401.1 SCOPE.
  
 3. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 UNDILUTED PROPANE (LP) SPECIFY 11.0 INCH WC, 2 PSI OR
 10 PSI.
  
 4. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 NOTE: THE PLANS DO HAVE A SIGNATURE, HOWEVER ALSO
 PLEASE PRINT THE NAME OF THE PERSON TAKING
 RESPONSIBILITY OF THE DRAWINGS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  