Plan Review Notes
Plan Review Notes For Permit 08040604
Permit Number 08040604
Review Stop E
Sequence Number 1
Notes
Date Text
2008-04-28 08:55:58 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1AS
 AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} LIGHTING SYSTEMS AND EQUIPMENT SHALL COMPLY WITH THE
 REQUIREMENTS OF 415.1.ABC AND APPLICABLE REQUIREMENTS
 OF SECTION 415.2. THIS SECTION SHALL APPLY TO THE
 FOLLOWING:
 1. INTERIOR SPACES OF BUILDINGS;
  
 SHOW COMPLIANCE WITH 13-415.2.B.1 (3). DETERMINE THE
 INTERIOR LIGHTING POWER ALLOWANCE BY USING THE COLUMNS
 DESIGNATED SPACE-BY-SPACE METHOD IN TABLE 415.2.B.
 MULTIPLY THE FLOOR AREA(S) OF THE SPACE(S) TIMES THE
 ALLOWED LIGHTING POWER DENSITY FOR THE SPACE TYPE THAT
 MOST CLOSELY REPRESENTS THE PROPOSED USE OF THE
 SPACE(S). THE PRODUCT IS THE LIGHTING POWER ALLOWANCE
 FOR THE SPACE(S). FOR SPACE TYPES NOT LISTED, SELECTION
 OF A REASONABLE EQUIVALENT CATEGORY SHALL BE PERMITTED.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718