Plan Review Notes
Plan Review Notes For Permit 08040604
Permit Number 08040604
Review Stop B
Sequence Number 1
Notes
Date Text
2008-05-03 14:52:35 
 BUILDING PLAN REVIEW
 PERMIT: 08040604
 ADD: 201 S. NARCISSUS AVE
 CONT: DESIGN CONTRACTING INC.
 TEL: (561)721-9214
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS, PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 2)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 3)2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 4)FBC 11-4.25 FIXED STORAGE FACILITIES SUCH AS
 CABINETS, SHELVES, CLOSETS, AND DRAWERS (MAIL BOXES)
 REQUIRE TO ACCESSIBLE BY SECTION 11-4.1 SHALL COMPLY
 WITH 11-4.25. ACCESSIBLE STORAGE SPACES SHALL BE WITHIN
 AT LEAST ONE OF THE REACH RANGES SPECIFIED IN SECTION
 11-4.2.5 AND 11-4.2.6 (SEE FIGURE 5 AND 6) ELEVATION
 DRAWINGS ARE REQUIRED SHOWING COMPLIANCE.
  
 5)IF THE HALLWAY OUTSIDE THE NEW OFFICE IS A RATED
 WALL, THE FILL IN SECTION SHALL MAINTAIN THAT RATING.
 IS A WINDOW BEING INSTALLED IN THE NEW WALL? IF SO
 PLEASE PROVIDE MORE DETAIL DRAWINGS AND INFORMATION
 INDICATING THE HEIGHT AND WIDTH OF THE WINDOW AND THE
 TYPE OF GLASS. ONE OF THE FIRE SPRINKLERS IS NOT SHOWN
 ON THE PROPOSED DRAWING, WILL IT BE REMOVED? WPB
 AMENDMENTS 106.1.2* ADDITIONAL INFORMATION IS
 REQUIRED.
  
 NOTE, IF THERE IS A UNIT OR SUITE NUMBER PLEASE
 INDICATE ON DRAWINGS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]