Plan Review Notes
Plan Review Notes For Permit 08040571
Permit Number 08040571
Review Stop E
Sequence Number 3
Notes
Date Text
2008-08-11 16:23:05 
 **DENIED3RD REVIEW**
  
 FIRST REVIEW UNDER PERMIT APPLICATION.
 SAME COMMENT FROM PREVIOUS REVIEW.
  
 1) NOTE:PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1 AND.1.2.
 THE NEW NOTE ON PLANS INDICATES A LIGHTING POWER USE OF
 160 WATTS WHICH IS NOT POSSIBLE BASED ON WHAT IS SHOWN
 ON PLANS.
 PLEASE SEE SECTION 13-415.2.ABC.1.1, .1.2. THE WATTAGE
 FOR TRACK LIGHTING SHALL BE BASED ON THE VA RATING OF
 EACH FIXTURE TIMES THE NUMBER OF FIXTURES OR 30VA PER
 FT OF TRACK WHICH EVER IS GREATER. BASED ON THE PLANS
 AND THE LENGTH OF TRACK THE TOTAL WATTAGE IS OVER 1200
 WHICH EXCEEDS THE MAXIMUM ALLOWED BY THE CODE.
 NO PERFORMANCE WAS GIVEN FOR OTHER LOCATIONS.
 PLEASE BE SURE TO COMPLETE ALL FIXTURE INFORMATION.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]