| Date |
Text |
| 2008-08-11 16:23:05 | |
| | **DENIED3RD REVIEW** |
| | |
| | FIRST REVIEW UNDER PERMIT APPLICATION. |
| | SAME COMMENT FROM PREVIOUS REVIEW. |
| | |
| | 1) NOTE:PLEASE SUBMIT LIGHTING PERFORMANCE |
| | CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1 AND.1.2. |
| | THE NEW NOTE ON PLANS INDICATES A LIGHTING POWER USE OF |
| | 160 WATTS WHICH IS NOT POSSIBLE BASED ON WHAT IS SHOWN |
| | ON PLANS. |
| | PLEASE SEE SECTION 13-415.2.ABC.1.1, .1.2. THE WATTAGE |
| | FOR TRACK LIGHTING SHALL BE BASED ON THE VA RATING OF |
| | EACH FIXTURE TIMES THE NUMBER OF FIXTURES OR 30VA PER |
| | FT OF TRACK WHICH EVER IS GREATER. BASED ON THE PLANS |
| | AND THE LENGTH OF TRACK THE TOTAL WATTAGE IS OVER 1200 |
| | WHICH EXCEEDS THE MAXIMUM ALLOWED BY THE CODE. |
| | NO PERFORMANCE WAS GIVEN FOR OTHER LOCATIONS. |
| | PLEASE BE SURE TO COMPLETE ALL FIXTURE INFORMATION. |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |