Date Text
2008-05-03 17:16:34DENIED
 REFERENCE: FBC-2004 PLUMBING W/2007 AMENDMENTS
 FBC-2004 FUEL GAS W/2007 AMENDMENTS
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUES
 CITY WPB MUNICIPAL CODE
  
 1. ALL ARCHITECTURAL SHEETS. CUBELLIS'S TITLE BLOCK
 ADDRESS DOES NOT REFLECT THE ADDRESS OF RECORD ON THE
 STATE OF FLORIDA DBPR WEBSITE.(97 LIBBEY INDUSTRIAL
 PARKWAY WEYMOUTH MA. ON TITLE BLOCK--1800 ELLERY DR
 BOSTON MA. ON DBPR WEBSITE). PLEASE UPDATE THE TITLE
 BLOCK OR THE DBPR WEBSITE PRIOR TO RESUBMITTING TO THE
 CITY FOR REVIEW. (SEE ATTACHED SHEET). FAC
 61G1-16.004(1) & FS 481.025.
  
 2. ALL PME & SPC SHEETS SHALL INCLUDE THE CERTIFICATE
 OF AUTHORIZATION FOR THE ENGINEERING COMPANY IN THE
 TITLE BLOCK OF EACH SHEET. ALSO THE ADDRESS FOR
 CUBELLIS INC IN INDICATED AS 711 ATLANTIC AVENUE BOSTON
 MA. ON THE FLORIDA STATE DBPR WEBSITE WHICH DOES NOT
 REFLECT THE ADDRESS INDICATED IN THE TITLE BLOCK OF
 EACH SHEET. (97 LIBBEY INDUSTRIAL PARKWAY WEYMOUTH MA).
 PLEASE UPDATE THE TITLE BLOCK OR THE DBPR WEBSITE PRIOR
 TO RESUBMITTING TO THE CITY FOR REVIEW. (SEE ATTACHED
 SHEET). FAC 61G15-23.002(2) & FS 471.2055
  
 3. SHT P-1 REFRIGERATION TUBING PLAN. WORK INDICATED IN
 MECHANICAL AND SHALL BE SUBMITTED IN THE MECHANICAL
 PLANS, NOT THE PLUMBING PLANS. PLEASE SUBMIT UNDER
 MECHANICAL PLANS. FS 489.
  
 4. SHT P-2 DRAWING NOTES #11 AND WASTE PIPING PLAN
 PIPING TO & INCLUDING THE GREASE INTERCEPTOR ARE NOT
 APPROVED. ARTICLE III SECTION 90-124(7)(B). PLEASE
 CONNECT ROTISSERIE TO EXISTING GREASE SYSTEM TO CATCH
 MINIMUM AMOUNT OF GREASE. THE ROTISSERIE SHALL DRAIN
 INTO A CONTAINER WHICH SHALL CATCH THE GREASE AND BE
 DISPOSED OF PROPERLY WITH OUT DRAINING INTO THE
 SYSTEM.
  
 5. SHT P-3 WATER DISTRIBUTION NOTE #7 WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES, IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING. SECTION 604.9 &
 PDI-WH 201.
  
 6. SHT P-5 SHOW THE CHANGE IN LOCATION FOR THE WATER
 CLOSET AND THE LAV IN THE ACCESSIBLE STALLS ON THE
 SANITARY RISER DIAGRAM. SECTION 106.3.5.1.3.
  
 7. SHT P-5 GREASE INTERCEPTOR AT ROTISSERIE IS NOT
 APPROVED. ARTICLE III SECTION 90-124(7)(B).
  
 8. SHT P-5 INDICATE WHERE THE BRANCH LINE CONNECTS TO
 THE BUILDING GREASE DRAIN LINE DOWNSTREAM OF THE
 ROTISSERIE. SECTION 106.1.2.
  
 9. SHT P-6 SHOW THE CHANGE IN LOCATION FOR THE WATER
 CLOSET AND THE LAV IN THE ACCESSIBLE STALLS ON THE
 WATER RISER DIAGRAM. SECTION 106.3.5.1.3.
  
 10 SHT P-6 A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT
 THE FOLLOWING INFORMATION FOR PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. INDICATE THE LENGTH OF PIPING FROM THE
 GAS METER TO THE GENERATOR.
  
 B. TYPE OF GAS, (LP OR NATURAL).
  
 C. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). ALSO INDICATE THE BTU LOAD FOR THE
 GENERATOR.
  
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. (NEW EQUIPMENT).
  
 E. INDICATE THE PIPE SIZE FROM THE METER TO THE FIRST
 TEE AND THE EXISTING PIPE SIZE TO THE GENERATOR.
  
 F. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. PLEASE
 INDICATE EACH VALVE AND UNION ON RISER.
  
 11. SHT P-7 THE PLUMBING LEGEND AND SCHEDULE #50 AS
 WELL AS THE GREASE TRAP DETAIL ARE NOT APPROVED.
 ARTICLE III SECTION 90-124(7)(B). PLEASE DELETE FROM
 PLANS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  