Text |
| 2008-07-10 11:52:43 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS W/2007 AMENDMENTS |
| | |
| | 1. SHT P-6 A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT |
| | THE FOLLOWING INFORMATION FOR PERMIT: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. INDICATE THE LENGTH OF PIPING FROM THE |
| | GAS METER TO THE GENERATOR. |
| | |
| | B. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | C. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). ALSO INDICATE THE BTU LOAD FOR THE |
| | GENERATOR. |
| | |
| | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. (NEW EQUIPMENT). |
| | |
| | E. INDICATE THE PIPE SIZE FROM THE METER TO THE FIRST |
| | TEE AND THE EXISTING PIPE SIZE TO THE GENERATOR. |
| | |
| | F. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. PLEASE |
| | INDICATE EACH VALVE AND UNION ON RISER. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |