| Plan Review Notes For Permit 08040571 |
| Permit Number |
08040571 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-05-22 16:43:59 | *****DENIED***** | | | | | | | | | 1. IN ADDITION TO THE FIRE CODE (FLORIDA FIRE | | | PREVENTION CODE 2004) LISTED ON SHEET T-1, NFPA 101, | | | LIFE SAFETY CODE, 2003 EDITION SHALL BE REFERENCED. | | | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | | BE REMOVED FORM THE SITE AT THE END OF EACH SHIFT OR | | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 4.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE | | | WITH ACCESS TO OR EGRESS FROM THE PROPERTY OR OTHER | | | TENANT SPACES IN THE PALM COAST SHOPPING PLAZA. | | | | | | 5.WILL THE BUILDING OR PORTION OF THE BUILDING BE | | | OCCUPIED DURING CONSTRUCTION, REPAIR, ALTERATIONS, OR | | | ADDITION? | | | | | | 6.SHOW EMERGENCY LIGHTING FOR THIS FACILITY. | | | | | | 7.SPECITY INTERIOR WALL AND CEILING FINISH MATERIALS | | | IN TERMS OF CLASS A OR CLASS B. | | | | | | 8.PROVIDE A LAYOUT OF THE FIRE ALARM SYTEM DEVICES | | | FOR THE BUILDING IN RELATION TO THE NEW SCOPE OF WORK. | | | | | | 9.PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS FOR | | | THE BUILDING IN RELATION TO THE NEW SCOPE OF WORK. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET | | | EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT.MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | |
|