| 2008-05-05 17:36:57 | ** DENIED** |
| | |
| | 1) NOTE: PLEASE SEE PLANS HAVE ONLY BEEN SUBMITTED FOR |
| | *PLAN REVIEW* ONLY AND HAVE NOT BEEN SUBMITTED FOR |
| | PERMIT. |
| | ONCE PLANS ARE FOUND TO BE CODE COMPLIANT REVIEWS WILL |
| | STILL REMAIN IN A FAILED STATUS UNTIL PERMIT IS APPLIED |
| | FOR BY A LICENSED CONTRACTOR. PLEASE KNOW ANY CODE |
| | CHANGES MAY AFFECT THE PLANS WHEN APPLICATION IS |
| | FINALLY MADE ALONG WITH OTHER LICENSING ITEMS WHICH ARE |
| | VERIFIED WHEN UNDER PERMIT APPLICATION. |
| | |
| | 2) NOTE: PLEASE SEE MISSING REQUIRED TITLE BLOCK |
| | INFORMATION FOR THE ARCHITECTURAL, ENGINEERING PLANS. |
| | PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION |
| | REQUIRED FOR BOTH FIRMS PER FS 481.219 FOR |
| | ARCHITECTURAL FIRM AND FS 471.023 FOR ENGINEERING |
| | FIRM. |
| | ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | ANY OTHER REVIEWER(S). |
| | |
| | 3) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED |
| | ON ELECTRICAL AND ARCHITECTURAL SHEETS. THESE ARE |
| | REQUIRED FOR THIS REVIEWER AT A MINIMUM. |
| | 2004 FBCW/2007 REVISIONS |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE SEE THE CODES AS LISTED ON PLANS ARE NOT |
| | APPLICABLE. THE STATE OF FLORIDA IS NOT UNDER IBC, IMC, |
| | IPCOR THE 2002 NEC. |
| | PLEASE SEE THE INCORRECT CODE FOR ENERGY COMPLIANCE IS |
| | ALSO NOTED. |
| | 2004 FBC W/2007 REVISIONS FOR FLORIDA ENERGY EFFICIENCY |
| | CODE. |
| | |
| | 4) NOTE: PLEASE VERIFY LIGHTING CONTROLS FOR ANY NEW |
| | LOCATIONS FOR SEPARATE SPACES IN BUILDINGS OVER 5K SQ |
| | FT. |
| | THIS WOULD APPLY TO NEW BATH ROOMS FOR EXAMPLE: PLEASE |
| | SEE OTHER AREAS AS NOTED IN SECTIONS BELOW. THESE NEED |
| | TO MEET *MINIMUM PRESCRIPTIVE REQUIREMENTS*. |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3 |
| | |
| | 5) NOTE: PLEASE SEE 13-415.2, 13-415.1.ABC.1.1, .1.2 |
| | FOR MINIMUM PERFORMANCE CALCULATIONS. |
| | |
| | 6) NOTE: PLEASE KNOW THIS IS FOR INFORMATIONAL PURPOSE. |
| | A CORRECTION NOTICE WAS ISSUED FOR THE LOCATION OF THE |
| | GENERATOR WHICH IS NOT PERMITTED IN THE MAIN ELECTRICAL |
| | ROOM. THIS IS A LIFE SAFETY AND FIRE HAZARD. |
| | PLEASE BE AWARE. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |