Plan Review Notes
Plan Review Notes For Permit 08040571
Permit Number 08040571
Review Stop E
Sequence Number 1
Notes
Date Text
2008-05-05 17:36:57** DENIED**
  
 1) NOTE: PLEASE SEE PLANS HAVE ONLY BEEN SUBMITTED FOR
 *PLAN REVIEW* ONLY AND HAVE NOT BEEN SUBMITTED FOR
 PERMIT.
 ONCE PLANS ARE FOUND TO BE CODE COMPLIANT REVIEWS WILL
 STILL REMAIN IN A FAILED STATUS UNTIL PERMIT IS APPLIED
 FOR BY A LICENSED CONTRACTOR. PLEASE KNOW ANY CODE
 CHANGES MAY AFFECT THE PLANS WHEN APPLICATION IS
 FINALLY MADE ALONG WITH OTHER LICENSING ITEMS WHICH ARE
 VERIFIED WHEN UNDER PERMIT APPLICATION.
  
 2) NOTE: PLEASE SEE MISSING REQUIRED TITLE BLOCK
 INFORMATION FOR THE ARCHITECTURAL, ENGINEERING PLANS.
 PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION
 REQUIRED FOR BOTH FIRMS PER FS 481.219 FOR
 ARCHITECTURAL FIRM AND FS 471.023 FOR ENGINEERING
 FIRM.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER REVIEWER(S).
  
 3) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED
 ON ELECTRICAL AND ARCHITECTURAL SHEETS. THESE ARE
 REQUIRED FOR THIS REVIEWER AT A MINIMUM.
 2004 FBCW/2007 REVISIONS
 2005 NFPA-70
 2003 NFPA-101
  
 ** PLEASE SEE THE CODES AS LISTED ON PLANS ARE NOT
 APPLICABLE. THE STATE OF FLORIDA IS NOT UNDER IBC, IMC,
 IPCOR THE 2002 NEC.
 PLEASE SEE THE INCORRECT CODE FOR ENERGY COMPLIANCE IS
 ALSO NOTED.
 2004 FBC W/2007 REVISIONS FOR FLORIDA ENERGY EFFICIENCY
 CODE.
  
 4) NOTE: PLEASE VERIFY LIGHTING CONTROLS FOR ANY NEW
 LOCATIONS FOR SEPARATE SPACES IN BUILDINGS OVER 5K SQ
 FT.
 THIS WOULD APPLY TO NEW BATH ROOMS FOR EXAMPLE: PLEASE
 SEE OTHER AREAS AS NOTED IN SECTIONS BELOW. THESE NEED
 TO MEET *MINIMUM PRESCRIPTIVE REQUIREMENTS*.
 13-415.1.ABC.1.1, .1.2 AND .1.3
  
 5) NOTE: PLEASE SEE 13-415.2, 13-415.1.ABC.1.1, .1.2
 FOR MINIMUM PERFORMANCE CALCULATIONS.
  
 6) NOTE: PLEASE KNOW THIS IS FOR INFORMATIONAL PURPOSE.
 A CORRECTION NOTICE WAS ISSUED FOR THE LOCATION OF THE
 GENERATOR WHICH IS NOT PERMITTED IN THE MAIN ELECTRICAL
 ROOM. THIS IS A LIFE SAFETY AND FIRE HAZARD.
 PLEASE BE AWARE.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717