| 2008-05-08 10:16:50 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.DECLARE LEVEL OF ALTERATION, FBC EXISTING BUILDING |
| | CODE, CHAPTER 3. |
| | |
| | 2.PLEASE REVISE GOVERNING CODE TO INCLUDE 2007 |
| | REVISIONS/SUPPLEMENTS. |
| | |
| | 3.INFORMATIONAL; THIS IS A PLAN CHECK ONLY.THE |
| | REVIEW WILL REMAIN IN FAILED STATUS UNTIL A CONTRACTOR |
| | LICENSED TO DO THE WORK HAS APPLIED FOR PERMIT, AND ALL |
| | PLAN REVIEW ISSUES HAVE BEEN ADDRESSED. |
| | |
| | 4.CERTIFICATE OF AUTHORIZATION REQUIRED FOR ENGINEER, |
| | ARCHITECT, TO PRACTICE THROUGH A COMPANY, FS481.219(2), |
| | FS471.023, AND THE LICENSE NUMBER IS TO PRINTED ON EACH |
| | SHEET, FAC61G1-16, FAC61G15-23.002. |
| | |
| | 5.SHEET A8, FIGURE 30E, REVISE GRAB BAR DISTANCE FROM |
| | CORNER.THE PLAN STATES 6IN MIN; THIS SHOULD BE 6IN |
| | MAX FBC FIGURE 11-30E. |
| | |
| | 6.PLEASE SEE FBC11-4.28, ALARMS.PLEASE SHOW |
| | COMPLIANCE ON THE PLAN, IN THE FORM OF A GENERAL NOTE |
| | AND ALSO IN AREAS SUCH AS BATHROOMS.THE PLAN STATES |
| | ON E1, GENERAL NOTE 31, THAT FIRE ALARM IS NOT WITHIN |
| | THE SCOPE OF THIS PERMIT.HOWEVER, COMPLIANCE WITH |
| | ACCESSIBILITY REQUIREMENTS (SUCH AS ADDING |
| | AUDIBLE/VISUAL ALARMS IN THE BATHROOMS AND OTHER |
| | GENERAL USE AREAS IF CURRENTLY NONE EXIST) MAY BE |
| | REQUIRED.FBC11-4.1.6(1)(B). |
| | |