Plan Review Notes
Plan Review Notes For Permit 08040571
Permit Number 08040571
Review Stop B
Sequence Number 1
Notes
Date Text
2008-05-08 10:16:50****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.DECLARE LEVEL OF ALTERATION, FBC EXISTING BUILDING
 CODE, CHAPTER 3.
  
 2.PLEASE REVISE GOVERNING CODE TO INCLUDE 2007
 REVISIONS/SUPPLEMENTS.
  
 3.INFORMATIONAL; THIS IS A PLAN CHECK ONLY.THE
 REVIEW WILL REMAIN IN FAILED STATUS UNTIL A CONTRACTOR
 LICENSED TO DO THE WORK HAS APPLIED FOR PERMIT, AND ALL
 PLAN REVIEW ISSUES HAVE BEEN ADDRESSED.
  
 4.CERTIFICATE OF AUTHORIZATION REQUIRED FOR ENGINEER,
 ARCHITECT, TO PRACTICE THROUGH A COMPANY, FS481.219(2),
 FS471.023, AND THE LICENSE NUMBER IS TO PRINTED ON EACH
 SHEET, FAC61G1-16, FAC61G15-23.002.
  
 5.SHEET A8, FIGURE 30E, REVISE GRAB BAR DISTANCE FROM
 CORNER.THE PLAN STATES 6IN MIN; THIS SHOULD BE 6IN
 MAX FBC FIGURE 11-30E.
  
 6.PLEASE SEE FBC11-4.28, ALARMS.PLEASE SHOW
 COMPLIANCE ON THE PLAN, IN THE FORM OF A GENERAL NOTE
 AND ALSO IN AREAS SUCH AS BATHROOMS.THE PLAN STATES
 ON E1, GENERAL NOTE 31, THAT FIRE ALARM IS NOT WITHIN
 THE SCOPE OF THIS PERMIT.HOWEVER, COMPLIANCE WITH
 ACCESSIBILITY REQUIREMENTS (SUCH AS ADDING
 AUDIBLE/VISUAL ALARMS IN THE BATHROOMS AND OTHER
 GENERAL USE AREAS IF CURRENTLY NONE EXIST) MAY BE
 REQUIRED.FBC11-4.1.6(1)(B).
  