| 2008-05-20 08:08:57 | BUILDING PLAN REVIEW 2ND |
| | PERMIT: 08040560 |
| | ADD: 1501 S. FLAGLER DR. #7H |
| | CONT: JEFFREY GOMERSALL BLDG CONTR. |
| | TEL: (561)718-1866 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 5-19-08 |
| | REVIEW: 2ND |
| | ACTION: DENIED |
| | |
| | 1)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 2) OK |
| | |
| | **NOTED; FBC EXISTING LEVEL 2 ALTERATION INCLUDE THE |
| | RECONFIGURATION OF SPACE, THE ADDITION OR ELIMINATION |
| | OF ANY DOOR OR WINDOW, THE RECONFIGURATION OR EXTENSION |
| | OF ANY SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL |
| | EQUIPMENT. THE NEW WALL AND THE NEW DOOR WILL BE |
| | INCLUDED IN THE SECTION AS LEVEL 2 ALTERATION.** |
| | 3)2004 FBC EXISTING |
| | 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 303, 304 AND 305 OF THIS CODE. |
| | |
| | 4)OK |
| | 9)OK |
| | |
| | **NOTED, HOWEVER, THE CONSTRUCTION TYPE, USE AND |
| | OCCUPANCY AND THE FLOOD ZONE INFORMATION ON THE PLANS |
| | ARE INCORRECT. THIS BUILDING IS A HI-RISE; THEREFORE |
| | CONSTRUCTION TYPE VB WILL NOT MEET THE REQUIREMENTS OF |
| | A HI-RISE BUILDING. GROUP R3 IS ONE AND TWO FAMILY |
| | DWELLINGS. THE CORRECT FLOOD ZONE IS A5; THERE IS NO |
| | FLOOD ZONE IN THE CITY OF WEST PALM BEACH DESIGNATED AS |
| | ?NEAR COASTAL?.** |
| | 10)INDICATE THE TYPE OF CONSTRUCTION OF THE BUILDING |
| | PER 2004 FBC CHAPTER 6 AND TABLE 601. THIS INFORMATION |
| | IS REQUIRED FOR PLAN REVIEW TO DETERMINE THE TYPE OF |
| | MATERIALS WHICH ARE ALLOWED IN THE BUILDING. |
| | |
| | 11)OK |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |