| 2008-04-28 17:31:37 | |
| | |
| | DENIED |
| | |
| | 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL |
| | COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006 & 2007 |
| | AMENDMENTS PER 106.1.1 FBC* |
| | |
| | 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| | PER 108.3 FBC* |
| | |
| | 3)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON |
| | SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER |
| | ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE |
| | ADDED TO THE PERMIT APPLICATION FEES |
| | |
| | NOTE: FEES ARE DUE IN THE AMOUNT OF $370.62 FOR |
| | INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS |
| | REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW |
| | |
| | 4)PROVIDE 2 COPIES OF A RECENT SURVEY SHOWING THE |
| | PROPOSED BUILDING/ADDITION WITH ALL SIDE AND REAR |
| | SETBACKS |
| | |
| | 5)PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN |
| | COMPLIANCE WITH THE REQUIREMENTS OF R403.1 FBC RES. |
| | |
| | 6)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2 |
| | FBC. BE SURE THAT THEY ARE SIGNED AND |
| | DATED BY PREPARER AND OWNER/AGENT PRIOR |
| | TO SUBMITTAL |
| | |
| | 7)PROVIDE SMOKE ALARMS TO EXISTING BUILDING PER |
| | R313.1.1 FBC RES. |
| | |
| | 8)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF |
| | EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE |
| | SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES. |
| | ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG |
| | |
| | 9)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE |
| | 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| | 10)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA |
| | STATE PRODUCT APPROVAL SHEETS WHEN AVAILABLE. THEY CAN |
| | BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG.WHEN |
| | AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE DENIED |
| | ***PLEASE NOTE THAT NEW APPROVAL WILL REQUIRE |
| | ARCHITECTS REVIEW AND APPROVAL***** |
| | |
| | 11)NO PRODUCT APPROVALS WERE SUBMITTED FOR LINTELS, |
| | |
| | 12)SUBMIT 2 COPIES OF ENGINEERED TRUSS DRAWINGS THAT |
| | COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR |
| | BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND |
| | APPROVED BY THE DESIGNER OF RECORD |
| | |
| | 13)PROVIDE ROOF VENTILATION ON DRAWINGS THAT COMPLIES |
| | WITH R806.1 & 806.2 FBC RES. |
| | |
| | 14)PROVIDE THE WIND DESIGN DATA THAT APPLIES TO |
| | BUILDING PER 1603.1.4 FBC PLEASE NOTE THAT THE 2006 |
| | AMENDMENTS TO THE 2004 FBC REQUIRE BUILDINGS LOCATED |
| | WITHIN EXP B TYPE TERRAIN THAT IS DIRECTLY ADJACENT TO |
| | EXP C TYPE TERRAIN SUCH AS OPEN GOLF COURSES AND BODIES |
| | OF WATER FOR A DISTANCE OF 600 FEET OR MORE IN ANY |
| | QUADRANT TO BE IN AN EXP C CATEGORY. PLEASE ADJUST THE |
| | DESIGN PARAMETERS AND WIND PRESSURES ACCORDINGLY |
| | |
| | 15)BUILDING ELEVATION TO INCLUDE MEAN ROOF HEIGHT |
| | |
| | 16)PROVIDE DOOR AND WINDOW TYPES AND SIZES ON THE |
| | DRAWINGS |
| | |
| | 17)THE PRODUCT APPROVALS FOR EXTERIOR DOORS HAS AN |
| | INVALID STATEWIDE APPROVAL NUMBER, THE MIAMI-DADE |
| | REPORT SUBMITTED IS UNDER FL # 253-R7 |
| | |
| | 18)THE STATEWIDE PRODUCT APPROVAL FOR ASPHALT |
| | SHINGLES HAS A UL COMPLIANCE REPORT AND INSTALLATION |
| | INSTRUCTIONS NOT THE MIAMI-DADE NOA THAT WAS SUBMITTED |
| | WITH IT, ALSO THE MIAMI-DADE NOA HAS EXPIRED. |
| | |
| | 19)PROVIDE MIN ROOF SHEATHING ATTACHMENT PER |
| | R803.2.3.1 FBC RES. MIN 8D RING SHANK NAILS |
| | |
| | 20)PROVIDE ATTIC ACCESS ON DRAWINGS TO ALL AREAS AS |
| | REQUIRED PER R807.1 FBC RES. |
| | |